CHV180 series frequency inverter special for elevator Detailed function description
.69.
Function
Code
Name
Description
Setting
Range
Factory
Setting
feedback
inspecting
interval
After selecting contactor control, the fault time of elevator relay action is greater han
P8.12, inverter will report contactor feedback fault (TbE).
Function
Code
Name
Description
Setting
Range
Factory
Setting
P8.13
Stop
contracting
brake
frequency
0.00~5.00Hz
0.00~5.00
0.00
This frequency is just set the point witch the inverter should break. If set P8.05,and it
starts timing when the inverter output frequency reaches the frequency point, output
the contracting brake signal when the time is over. The closing brake and contracting
brake of multi-function, output function been blocked at the same time. If P8.05 is set
to be 0, when the inverter output frequency reaches setting frequency point,
contracting brake is carried out immediately.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P8.14
Start DC
brake current
0.0~120%
0.0~120
0.0
P8.15
Start DC
brake time
0.0~50.0s
0.0~50.0
0.0
During starting, the inverter will perform DC braking at the set starting DC braking current,
after the time set by P8.15, it will accelerate.
When inverter is starting, DC brake is carried out according to the setting of P8.14 and
it is accelerated to run when the setting start DC brake time is reached. If P8.15 is set
to be 0, DC brake is invalid.
The bigger DC brake current is, the bigger braking torque
will be.
P8.15 should be greater than P8.06 when selecting first function of starting after DC
braking.