CHV180 series frequency inverter special for elevator Detailed function description
.48.
Function
Code
Name
Description
Setting
Range
Factory
Setting
limit
100.0% corresponds with the rated current of inverter.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P3.13
Reserved
0~65536
0~65536
0
P3.14
Reserved
0~65536
0~65536
0
6.5 P4 Group -- Encoder parameter
Function
Code
Name
Description
Setting
Range
Factory
Setting
P4.00
Encoder type
selection
0~2
0~2
1
When selecting the type of encoder, asynchronous motor and synchronous motor
need different PG cards, please refer to chapter 7.3 and 7.4 for wiring of encoder.
0: Increment encoder
1: SIN/COS encoder
The matching model is ERN1387, or the encoder is compatible with it’s’ signal.
2: UVM encoder
The pole number of encoder must be the same with that of the motor.
Note: When
P2.00=0
(asynchronous motor), only the increment encoder can be
chosen; when P2.01=1 (synchronous motor), only the SIN/COS and UVW
encoder can be chosen.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P4.01
PG pulse
number
1~65536
1~65536
1000
P4.02
PG direction
selection
0~1
0~1
0
P4.01: Setting the number of encoder pulse per cycle.
Note: When P0.00 is set to be 1, P4.10 must be set correctly according to the
encoder parameter, otherwise the motor will run abnormally. If the motor still run
abnormally when P4.10 has been set correctly, please change the PG direction
(P4.02).
The autotuning should be performed again for synchronous motor