Before Test Run
A test run must be performed after the entire
system has been completely installed. Confirm
the following points before performing the test:
a) The indoor and outdoor units are properly
installed.
b) Piping and wiring are properly connected.
c) Ensure that there are no obstacles near the
inlet and outlet of the unit that might cause
poor performance or product malfunction.
d) The refrigeration system does not leak.
e) The drainage system is unimpeded and
draining to a safe location.
f) The heating insulation is properly installed.
The grounding wires are properly connected.
g)
h) The length of the piping and the added
refrigerant stow capacity have been
recorded.
i) The power voltage is the correct voltage
for the air conditioner.
CAUTION
Failure to perform the test run may result in
unit damage, property damage or personal
injury.
Test Run Instructions
1. Open both the liquid and gas stop valves.
2. Turn on the main power switch and allow the
unit to warm up.
3. Set the air conditioner to COOL mode.
4. For the Indoor Unit
a. Ensure the remote control and its buttons
work properly.
b. Ensure the louvers move properly and can
be changed using the remote control.
c. Double check to see if the room
temperature is being registered correctly.
d. Ensure the indicators on the remote
control and the display panel on the indoor
unit work properly.
e. Ensure the manual buttons on the indoor
unit works properly.
f. Check to see that the drainage system is
unimpeded and draining smoothly.
g. Ensure there is no vibration or abnormal
noise during operation.
5. For the Outdoor Unit
a. Check to see if the refrigeration system is
leaking.
b. Make sure there is no vibration or
abnormal noise during operation.
c. Ensure the wind, noise, and water
generated by the unit do not disturb your
neighbors or pose a safety hazard.
6. Drainage Test
a. Ensure the drainpipe flows smoothly. New
buildings should perform this test before
finishing the ceiling.
b. Remove the test cover. Add 2,000ml of
water to the tank through the attached
tube.
c. Turn on the main power switch and run
the air conditioner in COOL mode.
d. Listen to the sound of the drain pump to
see if it makes any unusual noises.
e. Check to see that the water is discharged.
It may take up to one minute before the
unit begins to drain depending on the
drainpipe.
f. Make sure that there are no leaks in any of
the piping.
g. Stop the air conditioner. Turn off the main
power switch and reinstall the test cover.
NOTE:
If the unit malfunctions or does not
operate according to your expectations,
please refer to the Troubleshooting section
of the Owner’s Manual before calling
customer service.
Test Run
10
Page 30
Summary of Contents for V7CI-24WiFiR/U7RS-24
Page 46: ...Indoor Unit Installation 07 4 3 5 1 2 Manual instalare O 04 10 E 12 12 14 E 18 18 19 20 21...
Page 47: ...7 Page 3 L N MC MC 6 7 8 10 9 11 12 23 23 24 31 31 32 33 37 38 39 27 28 29 R32 R290 R32 R290...
Page 48: ...4 Page 4 1 2 server 3 4 NEC CEC 5 6 7 8 EN 8 9 10 IEC 11 O 1...
Page 49: ...5 12 13 3mm 10mA RCD 30mA 14 15 16 17 18 19 20 21 22 23 24 25 1 3 1 2...
Page 50: ...6 1 2 3 4 5 6 7 R32 8 X m Xm2 R32 R290...
Page 53: ...9 1 o 2 3 4 12 5 o R32 R290...
Page 55: ...11 1 2 3 4 5 MC MC 6 7 8 Page 18...
Page 56: ...12 Page 10 3 A 1 2 4 3 6 7 8 8 9 5 1 2 3 4 5 6 7 8 9...
Page 57: ...13 A 1m 3 2 1m 3 2 2 5m 8 B 1 2 4 3 6 7 8 8 9 5 1 2 3 4 5 6 7 8 9...
Page 58: ...14 E 3 2 X X X X X X X X X 1 1m 39 3 2 A A 250cm 98 4 Page 21 B...
Page 62: ...18 Page 14 60cm 23 6 Page 14 60cm 23 6 E 4 E 4 1 E 4 3 1 5 1 5 2 1 1 2 M10 E 4 2 90...
Page 70: ...26 Page 22 Page 22 6 7 8 9 E 6 10 10cm 3 9 90 3 1 2 3 1 2...
Page 71: ...27 Page 23 3mm 0 118 T3 15A 250VAC T5A 250VAC R32 T20A 250VAC 7 32 o o...
Page 77: ...33 Page 28 V7CRI 12WiFiR V7CRI 18WiFiR 1 1 2 9 2 45 1 2 1 2 M5 E 9 1 E 9 2 E 9 4 E 9 3...
Page 79: ...35 Page 45 4 6mm 1 2 2 1 3 4 6mm 0 2 0 3 4...
Page 80: ...36 Page 46...
Page 81: ...37 Page 30 5 6 2 000ml COOL 1 2 3 COOL 4 10...
Page 82: ...38 Page 30 11 O...
Page 83: ...39 Page 31 R32 R290 12 1 2 3 4 5 CO2 6 7...
Page 84: ...40 8 l l l l l 9 l l l 10 10 1 10 2 l l...
Page 85: ...41 11 12 13 14 LFL 25 OFN 15 l l l l l...
Page 86: ...42 OFN OFN OFN 16 l l l l l l OFN 17 l l l l...
Page 87: ...43 80 18 19 l l l l l l l...
Page 88: ...44 20 1 2 3 4 5...
Page 89: ...45 211 300 3300 www inventoraircondition gr media library...
Page 175: ...Seite 45...