![INVENTOR V7CI-24WiFiR/U7RS-24 Installation Manual Download Page 31](http://html1.mh-extra.com/html/inventor/v7ci-24wifir-u7rs-24/v7ci-24wifir-u7rs-24_installation-manual_2084174031.webp)
Page 31
VOLT
VOLT
VOLT
VOLT
VOLT
VOLT
VOLT
VOLT
Independent Power Supply Specifications
MODEL
(Btu/h)
≤
18K
19K~24K 25K~36K 37K~48K 49K~60K
POWER
(indoor)
PHASE
1 Phase
1 Phase
1 Phase
1 Phase
1 Phase
208-240V 208-240V
208-240V
208-240V
208-240V
CIRCUIT BREAKER/
FUSE(A)
15/10
15/10
15/10
15/10
15/10
POWER
(outdoor)
PHASE
1 Phase
1 Phase
1 Phase
1 Phase
1 Phase
208-240V 208-240V
208-240V
208-240V
208-240V
CIRCUIT BREAKER/
FUSE(A)
25/20
32/25
50/40
70/55
70/60
MODEL
(Btu/h)
≤
18K
19K~24K 25K~36K 37K~48K 49K~60K
POWER
(indoor)
PHASE
1 Phase
1 Phase
1 Phase
1 Phase
1 Phase
220-240V 220-240V
220-240V
220-240V
220-240V
CIRCUIT BREAKER/
FUSE(A)
15/10
15/10
15/10
15/10
15/10
POWER
(outdoor)
PHASE
1 Phase
1 Phase
1 Phase
1 Phase
1 Phase
208-240V 208-240V
208-240V
208-240V
208-240V
CIRCUIT BREAKER/
FUSE(A)
25/20
25/20
40/30
50/40
50/40
MODEL
(Btu/h)
≤
36K
37K~60K
≤
36K
37K~60K
POWER
(indoor)
PHASE
1 Phase
1 Phase
1 Phase
1 Phase
208-240V
208-240V
208-240V
208-240V
CIRCUIT BREAKER/FUSE(A)
15/10
15/10
15/10
15/10
POWER
(outdoor)
PHASE
3 Phase
3 Phase
3 Phase
3 Phase
380-420V
380-420V
208-240V
208-240V
CIRCUIT BREAKER/FUSE(A)
25/20
32/25
32/25
45/35
MODEL
(Btu/h)
≤
36K
37K~60K
≤
36K
37K~60K
POWER
(indoor)
PHASE
1 Phase
1 Phase
1 Phase
1 Phase
220-240V
220-240V
220-240V
220-240V
CIRCUIT BREAKER/FUSE(A)
15/10
15/10
15/10
15/10
POWER
(outdoor)
PHASE
3 Phase
3 Phase
3 Phase
3 Phase
380-420V
380-420V
208-240V
208-240V
CIRCUIT BREAKER/FUSE(A)
25/20
32/25
32/25
40/30
Inverter Type A/C Power Specifications
Page 26
Air Evacuation
Safety Precautions
CAUTION
• Use a vacuum pump with a gauge reading
lower than -0.1MPa and an air discharge
capacity above 40L/min.
• The outdoor unit does not need vacuuming.
DO NOT
open the outdoor unit’s gas and
liquid stop valves.
• Ensure that the Compound Meter reads
-0.1MPa or below after 2 hours. If after
three hours of operation and the gauge
reading is still above -0.1MPa, check if
there is a gas leak or water inside the pipe.
If there is no leakage, perform another
evacuation for 1 or 2 hours.
•
DO NOT
use refrigerant gas to evacuate
the system.
Evacuation Instructions
Before using manifold gauge and vacuum pump,
read their operation manuals to familiarize
yourself with how to use them properly.
Manifold Gauge
Compound gauge
-76cmHg
Low pressure valve
High pressure valve
Charge hose
Charge hose
Vacuum pump
Pressure gauge
Low pressure valve
Fig. 8.1
1. Connect the charge hose of the manifold
gauge to service port on the outdoor unit’s
low pressure valve.
2. Connect another charge hose from the
manifold gauge to the vacuum pump.
3. Open the Low Pressure side of the manifold
gauge.Keep the High Pressure side closed.
4. Turn on the vacuum pump to evacuate the
system.
5. Run the vacuum for at least 15 minutes, or
until the Compound Meter reads -76cmHG
(-1x105Pa).
6. Close the Low Pressure side of the manifold
gauge, and turn off the vacuum pump.
7. Wait for 5 minutes, then check that there has
been no change in system pressure.
NOTE:
If there is no change in system pressure,
unscrew the cap from the packed valve (high
pressure valve). If there is a change in system
pressure, there may be a gas leak.
8. Insert hexagonal wrench into the packed valve
(high pressure valve) and open the valve by
turning the wrench in a 1/4 counterclockwise
turn. Listen for gas to exit the system, then
close the valve after 5 seconds.
Flare nut
Cap
Valve body
Valve stem
Fig. 8.2
9. Watch the Pressure Gauge for one minute to
make sure that there is no change in pressure.
The Pressure Gauge should read slightly higher
than atmospheric pressure.
10.Remove the charge hose from the service port.
11.Using hexagonal wrench, fully open both the
high pressure and low pressure valves.
OPEN VALVE STEMS GENTLY
When opening valve stems, turn the hexagonal
wrench until it hits against the stopper.
DO NOT
try to force the valve to open further.
12.Tighten valve caps by hand, then tighten it
using the proper tool.
8
Summary of Contents for V7CI-24WiFiR/U7RS-24
Page 46: ...Indoor Unit Installation 07 4 3 5 1 2 Manual instalare O 04 10 E 12 12 14 E 18 18 19 20 21...
Page 47: ...7 Page 3 L N MC MC 6 7 8 10 9 11 12 23 23 24 31 31 32 33 37 38 39 27 28 29 R32 R290 R32 R290...
Page 48: ...4 Page 4 1 2 server 3 4 NEC CEC 5 6 7 8 EN 8 9 10 IEC 11 O 1...
Page 49: ...5 12 13 3mm 10mA RCD 30mA 14 15 16 17 18 19 20 21 22 23 24 25 1 3 1 2...
Page 50: ...6 1 2 3 4 5 6 7 R32 8 X m Xm2 R32 R290...
Page 53: ...9 1 o 2 3 4 12 5 o R32 R290...
Page 55: ...11 1 2 3 4 5 MC MC 6 7 8 Page 18...
Page 56: ...12 Page 10 3 A 1 2 4 3 6 7 8 8 9 5 1 2 3 4 5 6 7 8 9...
Page 57: ...13 A 1m 3 2 1m 3 2 2 5m 8 B 1 2 4 3 6 7 8 8 9 5 1 2 3 4 5 6 7 8 9...
Page 58: ...14 E 3 2 X X X X X X X X X 1 1m 39 3 2 A A 250cm 98 4 Page 21 B...
Page 62: ...18 Page 14 60cm 23 6 Page 14 60cm 23 6 E 4 E 4 1 E 4 3 1 5 1 5 2 1 1 2 M10 E 4 2 90...
Page 70: ...26 Page 22 Page 22 6 7 8 9 E 6 10 10cm 3 9 90 3 1 2 3 1 2...
Page 71: ...27 Page 23 3mm 0 118 T3 15A 250VAC T5A 250VAC R32 T20A 250VAC 7 32 o o...
Page 77: ...33 Page 28 V7CRI 12WiFiR V7CRI 18WiFiR 1 1 2 9 2 45 1 2 1 2 M5 E 9 1 E 9 2 E 9 4 E 9 3...
Page 79: ...35 Page 45 4 6mm 1 2 2 1 3 4 6mm 0 2 0 3 4...
Page 80: ...36 Page 46...
Page 81: ...37 Page 30 5 6 2 000ml COOL 1 2 3 COOL 4 10...
Page 82: ...38 Page 30 11 O...
Page 83: ...39 Page 31 R32 R290 12 1 2 3 4 5 CO2 6 7...
Page 84: ...40 8 l l l l l 9 l l l 10 10 1 10 2 l l...
Page 85: ...41 11 12 13 14 LFL 25 OFN 15 l l l l l...
Page 86: ...42 OFN OFN OFN 16 l l l l l l OFN 17 l l l l...
Page 87: ...43 80 18 19 l l l l l l l...
Page 88: ...44 20 1 2 3 4 5...
Page 89: ...45 211 300 3300 www inventoraircondition gr media library...
Page 175: ...Seite 45...