Page 26
Page 22
Indoor
Indoor
Indoor
Outdoor
Outdoor
Outdoor
Precautions
- For ensuring throttled efficiency, please
mount the throttle as horizontally as possible.
- Wrap the supplied anti-shock rubber at
external of the throttle for denoise.
1 Anti-shock rubber
2 Throttle
NOTE:
Use both a spanner and a torque
wrench when connecting or disconnecting
pipes to/from the unit.
Fig. 6.9
NOTE ON MINIMUM BEND RADIUS
Carefully bend the tubing in the middle
according to the diagram below.
DO NOT
bend the tubing more than 90° or more than
3 times.
Bend the pipe with thumb
min-radius 10cm (3.9”)
Fig. 6.10
6. After connecting the copper pipes to the
indoor unit, wrap the power cable, signal
cable and the piping together with binding
tape.
NOTE: DO NOT
intertwine signal cable with
other wires. While bundling these items
together, do not intertwine or cross the
signal cable with any other wiring.
7. Thread this pipeline through the wall and
connect it to the outdoor unit.
8. Insulate all the piping, including the valves
of the outdoor unit.
9. Open the stop valves of the outdoor unit
to start the flow of the refrigerant between
the indoor and outdoor unit.
CAUTION
Check to make sure there is no refrigerant
leak after completing the installation work.
If there is a refrigerant leak, ventilate the area
immediately and evacuate the system (refer
to the Air Evacuation section of this manual).
Installation Of The Throttle. (Some Models)
1 Throttle
2 Liquid pipe
3 Gas pipe
CAUTION
•
Ensure to wrap insulation around the
piping. Direct contact with the bare piping
may result in burns or frostbite.
•
Make sure the pipe is properly connected.
Over tightening may damage the bell
mouth and under tightening may lead to
leakage.
Page 23
Wiring
7
Safety Precautions
WARNING
• Be sure to disconnect the power supply
before working on the unit.
• All electrical wiring must be done
according to local and national regulations.
• Electrical wiring must be done by a
qualified technician. Improper connections
may cause electrical malfunction, injury
and fire.
• An independent circuit and single outlet
must be used for this unit.
DO NOT
plug
another appliance or charger into the same
outlet. If the electrical circuit capacity is not
enough or there is a defect in the electrical
work, it can lead to shock, fire, unit and
property damage.
• Connect the power cable to the terminals
and fasten it with a clamp. An insecure
connection may cause fire.
• Make sure that all wiring is done correctly
and the control board cover is properly
installed. Failure to do so can cause
overheating at the connection points, fire,
and electrical shock.
• Ensure that main supply connection is
made through a switch that disconnects
all poles, with contact gap of a least 3mm
(0.118”).
•
DO NOT
modify the length of the power
cord or use an extension cord.
CAUTION
• Connect the outdoor wires before
connecting the indoor wires.
• Make sure you ground the unit. The
grounding wire should be away from gas
pipes, water pipes, lightning rods,
telephone or other grounding wires.
Improper grounding may cause electrical
shock.
•
DO NOT
connect the unit with the power
source until all wiring and piping is
completed.
• Make sure that you do not cross your
electrical wiring with your signal wiring, as
this can cause distortion and interference.
Follow these instructions to prevent distortion
when the compressor starts:
• No other equipment should be connected
to the same power circuit.
• The unit’s power information can be found
on the rating sticker on the product.
• The unit must be connected to the main
outlet. Normally, the power supply must
have a low output impedance of 32 ohms.
NOTE:
The fuse is made of ceramic.
TAKE NOTE OF FUSE SPECIFICATIONS
The air conditioner s circuit board(PCB) is
designed with a fuse to provide overcurrent
protection. The specifications of the fuse are
printed on the circuit board, such as:
Indoor unit:
T3.15A/250VAC, T5A/250VAC.
(applicable for unit adopts R32 refrigerant)
Outdoor unit:
T20A/250VAC.
,
Summary of Contents for V7CI-24WiFiR/U7RS-24
Page 46: ...Indoor Unit Installation 07 4 3 5 1 2 Manual instalare O 04 10 E 12 12 14 E 18 18 19 20 21...
Page 47: ...7 Page 3 L N MC MC 6 7 8 10 9 11 12 23 23 24 31 31 32 33 37 38 39 27 28 29 R32 R290 R32 R290...
Page 48: ...4 Page 4 1 2 server 3 4 NEC CEC 5 6 7 8 EN 8 9 10 IEC 11 O 1...
Page 49: ...5 12 13 3mm 10mA RCD 30mA 14 15 16 17 18 19 20 21 22 23 24 25 1 3 1 2...
Page 50: ...6 1 2 3 4 5 6 7 R32 8 X m Xm2 R32 R290...
Page 53: ...9 1 o 2 3 4 12 5 o R32 R290...
Page 55: ...11 1 2 3 4 5 MC MC 6 7 8 Page 18...
Page 56: ...12 Page 10 3 A 1 2 4 3 6 7 8 8 9 5 1 2 3 4 5 6 7 8 9...
Page 57: ...13 A 1m 3 2 1m 3 2 2 5m 8 B 1 2 4 3 6 7 8 8 9 5 1 2 3 4 5 6 7 8 9...
Page 58: ...14 E 3 2 X X X X X X X X X 1 1m 39 3 2 A A 250cm 98 4 Page 21 B...
Page 62: ...18 Page 14 60cm 23 6 Page 14 60cm 23 6 E 4 E 4 1 E 4 3 1 5 1 5 2 1 1 2 M10 E 4 2 90...
Page 70: ...26 Page 22 Page 22 6 7 8 9 E 6 10 10cm 3 9 90 3 1 2 3 1 2...
Page 71: ...27 Page 23 3mm 0 118 T3 15A 250VAC T5A 250VAC R32 T20A 250VAC 7 32 o o...
Page 77: ...33 Page 28 V7CRI 12WiFiR V7CRI 18WiFiR 1 1 2 9 2 45 1 2 1 2 M5 E 9 1 E 9 2 E 9 4 E 9 3...
Page 79: ...35 Page 45 4 6mm 1 2 2 1 3 4 6mm 0 2 0 3 4...
Page 80: ...36 Page 46...
Page 81: ...37 Page 30 5 6 2 000ml COOL 1 2 3 COOL 4 10...
Page 82: ...38 Page 30 11 O...
Page 83: ...39 Page 31 R32 R290 12 1 2 3 4 5 CO2 6 7...
Page 84: ...40 8 l l l l l 9 l l l 10 10 1 10 2 l l...
Page 85: ...41 11 12 13 14 LFL 25 OFN 15 l l l l l...
Page 86: ...42 OFN OFN OFN 16 l l l l l l OFN 17 l l l l...
Page 87: ...43 80 18 19 l l l l l l l...
Page 88: ...44 20 1 2 3 4 5...
Page 89: ...45 211 300 3300 www inventoraircondition gr media library...
Page 175: ...Seite 45...