Absolute maximum loads
Table 5
and Table show the maximum continuous loads that can be supported by two 17.2 Ah batteries or one
17.2 Ah battery. If the total standby current exceeds those listed in the table, you do not meet 24/72-hour
standby requirements. Other battery sizes are possible, but two 17.2 Ah batteries are the maximum battery size
supported. If your standby time is different, you can use the calculations in
Formulas
to calculate the total
standby battery power required. If the answer exceeds the battery size you have chosen, you must install
appropriate batteries or adjust the system configuration to meet the battery power requirements.
AL-4017.
AL-4617
Table 5.
Absolute maximum loads for the AL-4017
Required batteries
Maximum continuous load for 24/72 hr. standby with 15 min. alarm and 1 active card read/5 min.
24-hour
72-hour
Two 17.2 Ah
Maximum total 750 mA Maximum aux 500 mA Maximum total 325 mA Maximum aux 100 mA
One 17.2 Ah
Maximum total 500 mA Maximum aux 300 mA
_
_
Table 6.
Absolute maximum loads for the AL-4617
Required batteries
Maximum continuous load for 24/72 hr. standby with 15 min. alarm and 1 active card read/5 min.
24-hour
72-hour
Two 17.2 Ah
Maximum total 1200 mA Maximum aux 1000 mA Maximum total 325 mA Maximum aux 100 mA
One 17.2 Ah
Maximum total 500 mA
Maximum aux 300 mA
_
_
Summary of Contents for Alliance AL-4017
Page 1: ...Alliance AL 4017 AL 4617 Control Panel Installation Manual ...
Page 6: ...Alliance AL 4017 AL 4617 Control Panel Installation Manual vi ...
Page 8: ...Alliance AL 4017 AL 4617 Control Panel Installation Manual viii ...
Page 10: ...Alliance AL 4017 AL 4617 Control Panel Installation Manual x ...