UL compliance statement
To maintain compliance with UL365, UL609, and UL1610:
Mercantile premises alarm systems
1. Zone types 22, 28, 29, and 30 (auto reset) can not be used.
2. Force arming is not allowed (refer to the
Alliance System Programming Manual
).
3. Siren time should be programmed for no less than 15 minutes (refer to the
Alliance System Programming Manual
).
4. Siren delay time must be set to 0 seconds (refer to the
Alliance System Programming Manual
).
5. Total combined entry/exit time can not exceed 60 seconds (refer to the
Alliance System Programming Manual
).
6. Alarm sounding device must be powered by the control unit and the siren test must be programmed
YES
(refer to the
Alliance
System Programming Manual
).
7. Safe and vault supervision circuits must be programmed for 24-hour operations (refer to the
Alliance System Programming
Manual
).
8. The system must be programmed for 24-hour test reports to be sent to the control station (refer to the
Alliance System
Programming Manual
).
9. Dual zone operation is not permitted.
10. Reporting to central station 2, 3, and 4 must be set to
NO
(refer to the
Alliance System Programming Manual
).
11. Display shunted zones on LCD keypad must be set to
YES
(refer to the
Alliance System Programming Manual
).
12. Resets from RAS without code must be set to
NO
(refer to the
Alliance System Programming Manual
).
13. AC fail delay time must not exceed 240 minutes (refer to the
Alliance System Programming Manual
).
14. System tamper activates siren and strobe must be set to
YES
(refer to the
Alliance System Programming Manual
).
15. Latching system alarms must be set to
YES
(refer to the
Alliance System Programming Manual
).
16. Siren types must be set to
l
(refer to the
Alliance System Programming Manual
).
17. Enable PSTN line monitor must be set to
YES
(refer to the
Alliance System Programming Manual
).
18. Sirens only after fail to report must be set to
NO
(refer to the
Alliance System Programming Manual
).
Mercantile safe and vault
In addition to the above requirements, Mercantile Safe and Vault Alarm Systems must comply with the following:
1. Alarm sounding device output must be mechanically and eletrically protected (see hook-up label).
Bank safe and vault
In addition to the above requirements, Bank Safe and Vault Alarm Systems must comply with the following:
1. This equipment must be installed within a complete vault, a complete safe, or an extent number 1 stockroom.
2. The system must be programmed to inhibit disarming the system during closed hours (refer to the
Alliance System
Programming Manual
).
Note:
For Bank Safe and Vault applications, both the internal and external alarm sounding devices must be the UL tested Ademco, Model
AB12M. For Mercantile Premise and Mercantile Safe and Vault applications, the alarm sounding devices must be a UL Listed Burglar
Alarm bell or siren such as the Moose, Model MP135.
Note:
The maximum AUX Power output including comms bus power (max total):
24-Hour
72-Hour
AL-4017
500mA
100mA
AL-4617
1000mA
100mA
Summary of Contents for Alliance AL-4017
Page 1: ...Alliance AL 4017 AL 4617 Control Panel Installation Manual ...
Page 6: ...Alliance AL 4017 AL 4617 Control Panel Installation Manual vi ...
Page 8: ...Alliance AL 4017 AL 4617 Control Panel Installation Manual viii ...
Page 10: ...Alliance AL 4017 AL 4617 Control Panel Installation Manual x ...