![background image](http://html.mh-extra.com/html/interlogix/alliance-al-4017/alliance-al-4017_installation-manual_2076746013.webp)
3
2. Install the standoffs. Before the board can be installed, you must configure the appropriate standoffs.
Use male/female standoffs where threaded holes are aligned with the mounting holes on the board and
use clip-in standoffs where square holes are aligned with the mounting holes (
Figure 2
)
Figure 2. Standoff layouts
3. Install the transformer. Use two 6/32 x 1/4 in. screws to mount the transformer in the enclosure. Install
the rubber grommet into the transformer shield and mount it to the enclosure using four 6/32 x 1/4 in.
screws provided with the transformer (
Figure 1
on page 2).
4. It is important that you provide the proper grounding to the enclosure. Use two male/female standoffs
to secure both the earth ground and enclosure ground wires (
Figure 1
on page 2). When securing the
ground wires, use the internal tooth star washers provided with the enclosure between the standoff and
the wire connector. All connections should be tight and make a good electrical connection.
5. Install the tamper switch. Assemble the tamper switch (use the instructions provided with the tamper
switch). Use the three 6/32 x 1/4 in. screws provided to mount the tamper switch.
Mounting holes
Control
Optional
boards
Optional
boards
panel
Control
panel
Summary of Contents for Alliance AL-4017
Page 1: ...Alliance AL 4017 AL 4617 Control Panel Installation Manual ...
Page 6: ...Alliance AL 4017 AL 4617 Control Panel Installation Manual vi ...
Page 8: ...Alliance AL 4017 AL 4617 Control Panel Installation Manual viii ...
Page 10: ...Alliance AL 4017 AL 4617 Control Panel Installation Manual x ...