- 89 -
5 Troubleshooting
5
Chapter 5 Troubleshooting
5.1 Fault and Warning Grading
Fault and warning grading
Faults and alarms are graded into the following three levels based on degree of severity: NO.1 > NO.2 >
NO.3.
NO.1 non-resettable fault
NO.1 resettable fault
NO.2 resettable fault
NO.3 resettable warning
"Resettable" means that the keypad stops displays of faults/warnings once the "reset signal" is input.
To reset a fault/warning, use one of the following two methods:
Set 200D-02h=1 (fault reset enabled).
Enable the rising edge of the control word 0x6040 bit7 on the host controller.
To reset a NO.1 fault and a NO.2 fault, turn off the S-ON signal and input the fault reset signal.
To reset a NO.3 warning, directly input the fault reset signal.
■
Relevant function code:
Function
Code
Name
Setting Range
Function
Setting
Mode
Effective
Time
Default
200Dh-02h
Fault
reset
0: no operation
1: fault/warning reset
The keypad stops display for the
resettable faults and warnings.
After reset, the value restores to
"0: no operation."
At stop Immediate
0
Summary of Contents for SV820N Series
Page 128: ...127 6 Trial Running 6 2 The definition part of FB 3 Five function blocks in FB...
Page 143: ...142 6 Trial Running 6 3 Open Visual studio and create a New Twincat3 Project...
Page 146: ...145 6 Trial Running 6 Click OK Click OK...
Page 147: ...146 6 Trial Running 6 Click Yes Click OK...
Page 149: ...148 6 Trial Running 6 C The default RPDO list is as follows...
Page 150: ...149 6 Trial Running 6...
Page 152: ...151 6 Trial Running 6 7 Activate the configuration and switch over to the running mode Click...
Page 158: ...157 6 Trial Running 6 Create a new POU...
Page 159: ...158 6 Trial Running 6 Create a new FB add MC_power MC_jog MC_home MC_absolute MC_reset to FB...
Page 160: ...159 6 Trial Running 6 Call axis_motion in main Call the program in PLCTASK...
Page 181: ...Revision History Date Revised Version Revised Details May 2017 A00 First release...