103
December 2008 - InnoMedia
© 2001 InnoMedia. All rights reserved.
InnoMedia iPBX Administrative Guide
UPS LED on web page
Signal Interface on the Device Side
Pin3: AC Failure
Pin4: Replace Battery
Pin5: Missing Battery
Pin6: Low Battery
Web Monitor
Status Indicators
Blinking State
UPS State
Telemetry Signals
Steady Green
The UPS is on utility power. (AC Mode)
Pin 3: Low
Steady Yellow
The UPS is on battery power.
Pin 3: Open
Blinking Yellow
The battery is at a low state.
Pin 6: Open
Steady Red
The battery is missing.
Pin 5: Open
Blinking Red
The battery fails the Self Test. (Battery replace)
Pin 4: Open
UPS Trap Oids:
Oid
Name
Get / Trap
.1.3.6.1.4.1.3354.1.3.1.1.7.14
AcFailure
These 4 OIDs stand for the 4 corresponding PINs of eUPS,
iPBX will trap these OIDs all together whenever any of
the 4 PINs changes it’s status.
For the values, “1” means “true”, “2” means “false”.
.1.3.6.1.4.1.3354.1.3.1.1.7.15
ReplaceBattery
.1.3.6.1.4.1.3354.1.3.1.1.7.16
BatteryMissing
.1.3.6.1.4.1.3354.1.3.1.1.7.17
BatteryLow