62
Enea series devices
Installation and programming manual
A.1
Configuring Enea devices
The distinct serial number of each detector is shown on the device information label. Manual addressing is
unnecessary as the addressing phase is automatic. To address devices, connect them to the loop and work
through the following steps.
Figure 29 - The reverse side of Enea detectors
The serial number is shown on the information label [A] and on two smaller removable labels [B]. When
installing the devices, it is strongly advises to remove the small labels and place one on the system layout
and the other on the mounting base. This will facilitate device tracing and re-location operations.
Note:
Each loop supports up to 240 devices.
A.1.1 Re-addressing
After connecting the devices to the loop, you must then configure the loop.
The addressing phase allows the system to determine the serial number of each device connected to the
loop and assign a logic address (a number between 1 and 240). The system will use this number to
indentify the point during all the system programming operations.
From the panel: insert the jumper in programming-mode position,
<key>
,
Programming
,
Configuration
,
Loop
,
Ok
,
Loop parameters
, then select
INIM
as the type of protocol
and
4 Wires
as the wiring method by pressing
Ok
,
Esc
,
Auto configure
,
Readdress
Once this operation is complete (which may take several minutes), a summary screen - indicating the total
number of devices found - will be shown. Ensure that the number of devices found corresponds to the
number of devices actually installed.
Sounders
ES0010RE
Addressable loop-powered sounder unit in red enclosure
ES0020RE
Addressable loop-powered sounder&beacon unit in red enclosure
ES0010BE
Addressable loop-powered sounder unit in white enclosure
ES0020BE
Addressable loop-powered sounder&beacon unit in white
enclosure
ES0020
Loop-powered addressable warning sign
Driver
EITK1000
Kit for the configuration, maintenance and diagnostics of systems
using IRIS and ENEA series devices
EITK-DRV
Driver for zones with IRIS series devices or loops with ENEA
series devices
EITK-BASE
Base for IRIS and ENEA series detectors
EITK-PWSP
Power supply for the EITK-DRV driver
A
B
B