Installation and programming manual
Preparing the programming data
41
Chapter 9
Preparing the programming data
Before programming the panel, fire detectors, extinguishant module (if used) and loop points, set the
following values.
9.1
Set Time and date
From the panel:
<key>, Maintenance, Time and date
Navigate through the programming field and set the new values. The system will select the day of the week
automatically.
9.2
Setting delays and times
From the panel:
<key>, Programming, Options
Navigate through the programming field and set the new values.
9.2.1
Parameters
9.3
Other options
From the panel:
<key>, Programming, Options
Navigate through the programming field and set the new values.
9.3.1
Parameters
Delay mains failure
A delay (0 to 30 minutes) which much run before the mains failure event is signalled.
This delay avoids unnecessary signaling of brief 'Mains failure' events.
Delay dialler
The period (0 to 10 minutes) which the dialer allows before signaling a zone alarm.
Verify time
The time (0 to 10 minutes) required to verify the validity of alarms. If the point
(detector) exceeds the pre-set threshold value, it will be reset by the panel. If the
point (detector) exceeds the pre-set threshold value while the 'verify alarm' time is
running, it will trigger an alarm. If it does not, it will restore to standby status. Applies
to points with Verify=YES.
Silence time
The duration (0 to 10 minutes) of Silence status when the system is operating in Night
mode (starting from the moment the
SILENCE
key is pressed).
Filter time
The minimum time (expressed in seconds), after reset operations, that an alarm or fault
signal must be present on the line before being processed by the control panel. This filter
avoids accidental activation of fault or alarm signals caused by instant activation (for
example, when an elevator trolley violates the area covered by a linear smoke detector).
Lock reset
The period (0 to 30 minutes), after extinction activation, when reset operations are
not allowed. If a confirm extinction signal is sent to the extinction module during this
period, reset operations will be re-enabled.
Mon. visible
YES
Enables monitor event signaling on the display.
NO
Disables monitor event signaling on the display Events can be viewed in the events
log only (refer to paragraph
16.1
).
Mute buzzer
YES
Disables the buzzer on the control panel motherboard
Attention:
Option to be used only during the programming phase.
NO
The buzzer is operating properly.