52
Programming the extinguishant module
Installation and programming manual
12.3.3 Signals that activate the point
Manual
extinguish
Same as
MAN-EXT
input.
EXAMPLE: A point connected to a Start-extinction button located inside the
protected environment.
Lock
extinguish
Same as
STOP-EXT input
EXAMPLE: A point connected to a Stop-extinction button located inside the
protected environment.
Monitor
restore
YES
The signal can be reset (e.g.: by releasing the button).
NO
The signal will persist until
RESET
button on the panel is pressed.
Output
-------------
The point is not activated by any signal.
Extinguish
Point activated at the same time as the
RELEASED
output programmed as
“Extinguish”.
Pre-
extinguish
Point activated at the same time as the
PRE-EXT
output.
Confirm
extinguish
Point activated by a “Confirm extinguish” input point.
Lock
extinguish
Point activated by the activation of “Lock extinguish” input point or by the
STOP-
EXT
input.
Silenceable
YES
The output can be silenced.
NO
The output will remain active until the
RESET
button on the panel is pressed.
Duration
Length of time the outputs will remain active.