6
SSA-SVX06B-EN
Model Number Description
Model Number Description
All products are identified by a multiple-character model number that precisely identifies a particular type of
unit. An explanation of the alphanumeric identification code is provided. Its use will enable the owner/
operator, installing contractors, and service engineers to define the operation, specific components, and
other options for any specific unit.
Note:
When ordering replacement parts or requesting service, be sure to refer to the specific model number,
serial number, and DL number (if applicable) stamped on the unit nameplate.
DIGITS 1 - 3: Product Type
TWE = Split System Heat Pump/Cooling Air Handler
DIGITS 4 - 6: Nominal Gross Cooling Capacity (MBh)
DIGIT 7: Major Development Sequence
DIGIT 8: Electrical Characteristics
DIGITS 9 - 10: Factory Installed Options
DIGITS 11: Minor Design Sequence
* = Current Design Sequence
1
DIGITS 12: Service Digit
* = Current Design Sequence
1
T W E
2 4 0
E
3
0 0
**
*
1 2 3
4 5 6
7
8
9 10
11
12
061 = 5 Tons (60 Hz)
051 = 4.6 Tons (50 Hz)
090 = 7½ Tons (60 Hz)
076 = 6.25 Tons (50 Hz)
120 = 10 Tons (60 Hz)
101 = 8.33 Tons (50 Hz)
150 = 12½ Tons (60 Hz)
126 = 10.4 Tons (50 Hz)
180 = 15 Tons (60 Hz)
156 = 13 Tons (50 Hz)
240 = 20 Tons (60 Hz)
201 = 16.7 Tons (50 Hz)
D = Single Circuit
E = Dual Circuit
1 = 208-230/60/1
W = 575/60/3
3 = 208-230/60/3
D = 380-415/50/3
4 = 460/60/3
K = 380/60/3
00 = Packed Stock (Standard)
03 = 2-speed Variable Frequency Drive (VFD) Standard Motor Electromechanical Condenser only
04 = 2-speed Variable Frequency Drive (VFD) Oversized Motor Electromechanical Condenser only
R3 = Single Zone Variable Air Volume (VFD) Standard Motor - Reliatel Cond only
R4 = Single Zone Variable Air Volume (VFD) Oversized Motor - Reliatel Cond only
1
* = sequential alpha character