SSA-SVX06B-EN
27
Electrical Data - Standard, SZVAV and 2-Speed VFD
5
TWE061D4
TWE061E4
BAYHTRL405A 5
460/3/60
1
10
15
BAYHTRL410A 9.96
1
17
20
BAYHTRL415A 14.96
1
25
25
BAYHTRL425A 24.92
2
40
40
7½
TWE090D3
(f)
TWE090E3
(f)
BAYHTRL405A 5
1
11
15
BAYHTRL410A 9.96
1
19
20
BAYHTRL415A 14.96
1
26
30
BAYHTRL425A 24.92
2
41
45
BAYHTRL435A 34.88
2
56
60
10
TWE120D3
(f)
TWE120E3
(f)
BAYHTRL405A 5
1
12
15
BAYHTRL410A 9.96
1
20
20
BAYHTRL415A 14.96
1
27
30
BAYHTRL425A 24.92
2
42
45
BAYHTRL435A 34.88
2
57
60
5
TWE061DW
BAYHTRLW05A 5
575/3/60
1
8
15
BAYHTRLW10A 9.96
1
15
15
BAYHTRLW15A 14.96
1
21
20
BAYHTRLW25A 24.92
2
33
35
7½ TWE090DW
BAYHTRLW05A 5
1
11
15
BAYHTRLW10A 9.96
1
17
15
BAYHTRLW15A 14.96
1
23
25
BAYHTRLW25A 24.92
2
36
35
BAYHTRLW35A 34.88
2
48
45
10
TWE120DW
TWE120EW
BAYHTRLW05A 5
1
10
15
BAYHTRLW10A 9.96
1
16
15
BAYHTRLW15A 14.96
1
22
25
BAYHTRLW25A 24.92
2
35
35
BAYHTRLW35A 34.88
2
47
45
(a) kW ratings are at: 208/240V for 208-230V air handlers.
480V for 460V air handlers
600V for 575V air handlers
For other than rated voltage, capacity = (Voltage/Rated Voltage)
2
x Rated Capacity.
(b) Any power supply and circuits must be wired and protected in accordance with local codes.
(c) The HACR circuit breaker is for U.S.A. installations only.
(d) Field wire must be rated at least 75°C.
(e) Field wire must be rated at least 90°C.
(f) With motor field converted to 460V.
Table 7.
Unit Wiring with Electric Heat (Single Point Connection) — 5-10 Ton Standard Air Handlers — 60 Hz (continued)
Tons Used
With
Heater Model
No.
Heater KW
Rating
(a)
Unit Power
Supply Control
Stages
Minimum
Circuit
Ampacity
(b)
Maximum
Fuse or HACR
Circuit
Breaker
Size
(b)(c)