SSA-SVX06B-EN
29
Electrical Data - Standard, SZVAV and 2-Speed VFD
Table 9.
Unit Wiring with Electric Heat (Single Point Connection) — 12½ - 20 Ton Standard Air Handlers
Tons
Used With
Heater
Model No.
Heater KW
Rating
(a)
Unit Power
Supply
Control
Stages
Minimum Circuit
Ampacity
(b)
Maximum Fuse or
HACR Circuit
Breaker Size
(b)(c)
12½ TWE150E3
BAYHTRM310A 7.51/10.00
208-230/3/60
1
33.5/36.9
35/40
BAYHTRM320A 14.96/19.92
1
59.3/66.8
60/70
BAYHTRM330A 22.47/29.92
2
85.5/96.8
90/100
BAYHTRM350A 37.44/49.84
2
137.3/156.7
150/175
15
TWE180E3
BAYHTRM310A 7.51/10.00
1
37.8/41.6
45/45
BAYHTRM320A 14.96/19.92
1
63.7/71.4
70/80
BAYHTRM330A 22.47/29.92
2
89.8/101.5
90/110
BAYHTRM350A 37.44/49.84
2
141.6/161.4
(d)
150/175
20
TWE240E3
BAYHTRM310A 7.51/10.00
1
44.1/49
60/60
BAYHTRM320A 14.96/19.92
1
71/79
80/90
BAYHTRM330A 22.47/29.92
2
97/109
100/110
BAYHTRM350A 37.44/49.84
2
149/169
(d)
150/175
12½ TWE150E3
(e)
BAYHTRM410A 10
460/3/60
1
19
20
BAYHTRM420A 19.92
1
34
35
BAYHTRM430A 29.92
2
49
50
BAYHTRM450A 49.84
2
79
80
15
TWE180E3
(e)
BAYHTRM410A 10
1
21
25
BAYHTRM420A 19.92
1
36
40
BAYHTRM430A 29.92
2
51
60
BAYHTRM450A 49.84
2
81
90
20
TWE240E4
BAYHTRM410A 10
1
24
30
BAYHTRM420A 19.92
1
39
40
BAYHTRM430A 29.92
2
54
60
BAYHTRM450A 49.84
2
84
90
(a) kW ratings are at: 208/240V for 208-230V air handlers.
480V for 460V air handlers
600V for 575V air handlers
For other than rated voltage, capacity = (Voltage/Rated Voltage)
2
x Rated Capacity.
(b) Any power supply and circuits must be wired and protected in accordance with local codes.
(c) The HACR circuit breaker is for U.S.A. installations only.
(d) Field wire must be rated at least 90°C.
(e) With motor field wired for 460V.