32
SSA-SVX06B-EN
Electrical Data - Standard, SZVAV and 2-Speed VFD
20
TWE240E3*3
BAYHTRM310A 7.51/10.00
208-230/3/60
1
43/47
45/50
BAYHTRM320A 14.96/19.92
1
69/77
70/80
BAYHTRM330A 22.47/29.92
2
95/107
100/110
BAYHTRM350A 37.44/49.84
2
147/167
150/175
TWE240E3*4
BAYHTRM310A 7.51/10.00
1
51/55
60/60
BAYHTRM320A 14.96/19.92
1
77/85
80/90
BAYHTRM330A 22.47/29.92
2
103/115
110/125
BAYHTRM350A 37.44/49.84
2
155/175
175/175
TWE240E4*3
BAYHTRM410A 10
460/3/60
1
23
25
BAYHTRM420A 19.92
1
38
40
BAYHTRM430A 29.92
2
53
60
BAYHTRM450A 49.84
2
83
90
TWE240E4*4
BAYHTRM410A 10
1
26
30
BAYHTRM420A 19.92
1
41
45
BAYHTRM430A 29.92
2
56
60
BAYHTRM450A 49.84
2
86
90
TWE240EW*3
BAYHTRMW10A 10
575/3/60
1
19
20
BAYHTRMW20A 19.92
1
32
35
BAYHTRMW30A 29.92
2
44
45
BAYHTRMW50A 49.84
2
69
70
TWE240EW*4
BAYHTRMW10A 10
1
22
25
BAYHTRMW20A 19.92
1
34
35
BAYHTRMW30A 29.92
2
47
50
BAYHTRMW50A 49.84
2
72
80
(a) kW ratings are at: 208/240V for 208-230V air handlers.
480V for 460V air handlers
600V for 575V air handlers
For other than rated voltage, capacity = (Voltage/Rated Voltage)
2
x Rated Capacity.
(b) Any power supply and circuits must be wired and protected in accordance with local codes.
(c) The HACR circuit breaker is for U.S.A. installations only.
Table 10. Unit Wiring with Electric Heat (Single Point Connection) — 12½ - 20 Ton SZVAV and 2-Speed VFD Air Handlers
Tons
Used With
Heater
Model No.
Heater KW
Rating
(a)
Unit Power
Supply
Control
Stages
Minimum
Circuit
Ampacity
(b)
Maximum Fuse
or HACR Circuit
Breaker
Size
(b)(c)