34
SSA-SVX06B-EN
Electrical Data - Standard, SZVAV and 2-Speed VFD
Table 13. Unit Wiring With Electric Heat (Single Point Connection) — Air Handlers
(a)(b)
(a) Field wire must be rated at least 167°F (75°C).
(b) Field wire must be rated at least 194°F (90°C).
Heater
Model No.
Heater
kW Rating
(c)
(c) kW ratings are at 400v for 3 phase, 400v air handlers
For other than rated voltage,
Capacity = (Voltage/Rated Voltage)
2
x Rated Capacity and kW = (Voltage/Rated Voltage)
2
Rated kW.
To Use
with Unit
Control
Stages
Minimum
Circuit
Ampacity
(d)
(d) Any power supply and circuits must be wired and protected in accordance with local codes. MCA and Maximum Fuse Size
is based on 400V.
Maximum
Fuse Breaker
Size
BAYHTRL405A
5.00
TWE051DD
1
13
15
BAYHTRL410A
9.96
1
22
25
BAYHTRL415A
14.96
1
31
35
BAYHTRL425A
24.92
2
49
50
BAYHTRL405A
5.00
TWE076DD
1
14
15
BAYHTRL410A
9.96
1
23
25
BAYHTRL415A
14.96
1
32
35
BAYHTRL425A
24.92
2
50
50
BAYHTRL435A
34.88
2
68
70
BAYHTRL405A
5.00
TWE101DD,
TWE101ED
1
14
15
BAYHTRL410A
9.96
1
23
25
BAYHTRL415A
14.96
1
32
35
BAYHTRL425A
24.92
2
50
50
BAYHTRL435A
34.88
2
68
70
BAYHTRM410A
10.00
TWE126ED
1
19
20
BAYHTRM420A
19.92
1
41
45
BAYHTRM430A
29.92
2
59
60
BAYHTRM450A
49.84
2
94
100
BAYHTRM410A
10.00
TWE156ED
1
23
25
BAYHTRM420A
19.92
1
41
45
BAYHTRM430A
29.92
2
59
60
BAYHTRM450A
49.84
2
95
100
BAYHTRM410A
10.00
TWE201ED
1
29
30
BAYHTRM420A
19.92
1
46
50
BAYHTRM430A
29.92
2
65
70
BAYHTRM450A
49.84
2
100
100