HandPunch 3000/4000 Manual
77
Figure 13-2: Earth Ground Connection Terminals
There are two standard methods for providing earth grounding to HandPunch
units:
• earth grounding all units (see 15)
• carrying an earth ground to each unit (see 16)
Earth ground all units when there is a good earth ground source near each unit
and/or when there are very long cable runs between units.
Carry an earth ground to each unit when there are no earth grounds convenient
to the unit and the unit’s power supply is floating.
Grounding
Terminal 1 and the center pin of jack J12 are connected together. Terminal 2 and
the sleeve of jack J12 are connected together.
Use any one of the following ground terminals to make the earth ground
connection: 8, 10, 12, 14, 18, 20, 22, 24, or 26. Do
NOT
use terminal 2 to
establish the earth ground connection; terminal 2 is not directly connected to
ground.
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
2625
SWITCH INPUTS
OUTPUTS
CARD
READER
INPUT
REX SWITCH
GR
OUND
DOOR SWITCH
GR
OUND
A
UX IN
1
GR
OUND
GR
OUND
GR
OUND
GR
OUND
GR
OUND
GR
OUND
GR
OUND
A
UX IN
2
+5
VD
C OUTPUT
D
AT
A
INPUT
CLOCK INPUT
LOCK OR CLOCK
BELL OR D
AT
A
A
UXOUT
1
A
U
XOUT
2
EARTH GROUND CONNECTION PINS
NOTE
NOTE
Summary of Contents for SCHLAGE HP-3000
Page 1: ...Terminal User s Guide HP 3000 4000...
Page 12: ...Introduction 10 This page is intentionally blank...
Page 24: ...Planning An Installation 22 This page is intentionally blank...
Page 32: ...Networking and Communications 30 This page is intentionally blank...
Page 44: ...Wiring Connections 42 This page is intentionally blank...
Page 46: ...Planning an Installation 44 This page intentionally blank...
Page 48: ...Planning an Installation 46 This page intentionally blank...
Page 52: ...Enter a Command Menu 50 This page is intentionally blank...