99/126
if
I28
=1 or 2, the fan stays on at speed 1.
if
I28
=4 or 5, the fan stays on at speed selected manually.
Speed 1 is activated and deactivated together with the heating/cooling output.
The hysteresis of speeds 2 and 3 is calculated automatically at 20% of the FB band (see
“3 speed on-off motor speed
control logic with on/off outputs” page 29
).
Example:
if
I18
=0.5°C, FB=2°C, the hysteresis of speeds 2 and 3 is 0.4°C in heating mode.
if
I19
=1.0°C, FB=3°C, the hysteresis of speeds 2 and 3 is 0.6°C in cooling mode.
N.B.: parameter
I25
is not used.