117/126
• BACnet signals
Analogue inputs
Object name
Object-ID
Description
Unit
Writable
INT_TEMP_COMP
ANALOG_INPUT:3002
Internal sensor temperature
°C / °F
No
TEMP_AI1
ANALOG_INPUT:3003
Remote sensor 1 temperature
°C / °F
No
TEMP_AI2
ANALOG_INPUT:3004
Remote sensor 2 temperature
°C / °F
No
INPUT_AI3
ANALOG_INPUT:3005
Remote sensor 3
°C / °F
ppm
%r.h.
No
INT_HUM_COMP
ANALOG_INPUT:3006
Internal humidity
%r.h.
No
If a temperature sensor is broken, the temperature visualized corresponds to values indicated on the table below:
Temperature of sensor with unit in °C (
I45
=0)
Value in °C
Sensor open
-20.0°C
Sensor with short-circuit
97.0°C
Temperature of sensor with unit in °F (
I45
=1)
Value in °F
Sensor open
-4.0°F
Sensor with short-circuit
206.6°F
For INPUT_AI3 set as 0...10V, if voltage in input is upper then 13.5V, the value 32000 indicating out of scale is put on Present_Value if RANGE_MAX_VOLT_
INPUT (Present_Value) - RANGE_MIN_VOLT_INPUT (Present_Value) is upper than 399, otherwise the value 3200 indicates out of scale.
Analogue values
Object name
Object-ID
Description
Unit
Writable
OUT_A
ANALOG_VALUE:3012 Value of output AO1
V
No
OUT_B
ANALOG_VALUE:3013 Value of output AO2
V
No
OUT_C
ANALOG_VALUE:3014 Value of output AO3
V
No
WORKING_TEMP
ANALOG_VALUE:3015 Operating temperature
°C / °F
No
WORKING_SET
(Note 1)
ANALOG_VALUE:3016 Operating setpoint
°C / °F
No
TOTAL_HOUR_OF_FAN
ANALOG_VALUE:3024 Number of hours of operation of fan
h
No
COR_INT_TEMP
(Note 3)
ANALOG_VALUE:2132 Internal temperature correction
°C / °F
Yes
COR_INT_HUM
ANALOG_VALUE:2133 Measured internal humidity correction
%r.h.
Yes
COR_REM_AI1
(Note 3)
ANALOG_VALUE:2134
External temperature correction AI1
°C / °F
Yes
COR_REM_AI2
(Note 3)
ANALOG_VALUE:2135
External temperature correction AI2
°C / °F
Yes
COR_REM_AI3
(Note 3)
ANALOG_VALUE:2136
External temperature correction AI3
°C / °F
Yes
WEIGHT_REM_AIR
ANALOG_VALUE:2137
Weighting (%) of external sensor AI1 in relation to the
internal sensor
%
Yes
ECO_SET_ADJUST
(Note 2)
ANALOG_VALUE:2143 Economy offset
°C / °F
Yes
HOL_SET_ADJUST
(Note 2)
ANALOG_VALUE:2144 “Not occupied holiday” mode offset
°C / °F
Yes
BASIC_ANTIFROST_SET
(Note 2)
ANALOG_VALUE:2145 Frost protection setpoint
°C / °F
Yes
WINTER_SET_CHANGEOVER
(Note 2)
ANALOG_VALUE:2146 Heating setpoint for automatic season changeover sensor
°C / °F
Yes
SUMMER_SET_CHANGEOVER
(Note 2)
ANALOG_VALUE:2147 Cooling setpoint for automatic season changeover sensor
°C / °F
Yes
SET_MIN_THERM
(Note 2)
ANALOG_VALUE:2148 Minimum thermostat setpoint
°C / °F
Yes
BASIC_HEAT_SET
(Note 2)
ANALOG_VALUE:2138 Heating setpoint for regulation other than 4 pipe system
°C / °F
Yes
BASIC_COOL_SET
(Note 2)
ANALOG_VALUE:2139 Cooling setpoint for regulation other than 4 pipe system
°C / °F
Yes
BASIC_SET_4_PIPE
(Note 2)
ANALOG_VALUE:2140 Setpoint for 4 pipe regulation
°C / °F
Yes
DO_HEATING_HYST
(Note 3)
ANALOG_VALUE:2149 Heating hysteresis for on/off output
°C / °F
Yes
DO_COOLING_HYST
(Note 3)
ANALOG_VALUE:2150 Cooling hysteresis for on/off output
°C / °F
Yes
DIFF_2_STAGES
(Note 3)
ANALOG_VALUE:2151 Differential between 2 stages
°C / °F
Yes
DEAD_ZONE
(Note 3)
ANALOG_VALUE:2152 Neutral zone for 4 pipe systems
°C / °F
Yes
PROP_BAND_HEAT
(Note 3)
ANALOG_VALUE:2153 Heating proportional band
°C / °F
Yes
PROP_BAND_COOL
(Note 3)
ANALOG_VALUE:2154 Cooling proportional band
°C / °F
Yes
INTEGRAL_TIME
ANALOG_VALUE:2155 Integral time
s
Yes
SW_PT_FAN_1
ANALOG_VALUE:2156 Speed 1 activation point for 3 speed motor
%
Yes
SW_PT_FAN_2
ANALOG_VALUE:2157 Speed 2 activation point for 3 speed motor
%
Yes
SW_PT_FAN_3
ANALOG_VALUE:2158 Speed 3 activation point for 3 speed motor
%
Yes