110/126
Address Description
Default
Min
Max
R/W
2188
FAN_SPEED_MODE
0=manual speed 1
1=manual speed 2
2=manual speed 3
3=automatic speed
3
0
3
R/W
2189
ON_OFF_MANUAL
0= OFF, 1= ON
1
0
1
R/W
2190
YEAR_SET
→
year to set
2012
2012
2100
R/W
2191
MONTH_SET
→
month to set
1
1
12
R/W
2192
DAY_SET
→
day to set
1
1
31
R/W
2193
HOUR_SET
→
time to set (hour)
0
0
23
R/W
2194
MIN_SET
→
time to set (min)
0
0
59
R/W
2195
ABI_CLOCK_SET_FROM_MODBUS
→
to update the clock via Modbus, set
the year, month, day, hour, minutes in order with addresses 2190 to 2194. The
set ABI_CLOCK_SET_FROM_MODBUS=1. The settings are automatically
loaded into the device and ABI_CLOCK_SET_FROM_MODBUS is reset to 0.
0
0
1
R/W
2196
RESET_PARAM_TO_DEFAULT
→
set parameter to 1 to reload the default
settings. The parameter resets to 0 once the procedure has terminated suc-
cessfully
0
0
1
R/W
2197
LOCK_KEYBOARD
0= keyboard not locked
1= keyboard locked
0
0
1
R/W
from
2198
to 2209
Reserved addresses (DEBUG)
R/W
2210
Major version of software (factory set)
-
-
-
R
2211
Minor version of software (factory set)
-
-
-
R
2212
Patch level of software (factory set)
-
-
-
R
2213
PUMP_RELAY
(see schedule page 16)
I53
0
0
1
R/W
2214
SEASON_BETWEEN_2P
(see schedule page 16)
I54
0
0
2
R/W
2215
RANGE_MIN_VOLT_INPUT
(see schedule page 16)
I55
0
-50
I56
R/W
2216
RANGE_MAX_VOLT_INPUT
(see schedule page 16)
I56
2000
I55
9999
R/W
2217
UNIT_VOLT_INPUT
(see schedule page 16)
I57
0
0
2
R/W
2218
COR_AI3_VOLT_INPUT
(see schedule page 16)
I58
0
-980
980
R/W
2219
ABIL_FAN
(see schedule page 16)
0= fan not used
1= fan used
I59
1
0
1
R/W
Note 1: set all temperature parameters with the same unit as parameter UNIT_C_F
The values are visualised multiplied by 10. For the setpoints in °F, the parameters
I12
and
I13
in °F and the OFFSET SETPOINT in °F, values visu-
alised are real values.
Note 2: the visualised value is equal to the value in Volt multiplied per 10 (example: value 80 = 8.0 V)
• Default parameters reset via MODBUS
The initial (default) configuration of the parameters can be reloaded as follows:
Set RESET_PARAM_TO_DEFAULT at address 2196 to 1.
The reset procedure starts. The display reports the following messages:
Li
Loading default settings...
Ld
Default settings loaded
When the default settings have been loading, the regulator returns to regulation mode and the register RESET_PARAM_
TO_DEFAULT in address 2196 resets to 0.