121/126
Object name
Object-ID
Description
Values / State text
Writable
VISU_TYPE_FIRST_DISP
MULTISTATE_VALUE:2173
Value displayed on display A
1=Int. sensor
2=Sensor AI1
3=Sensor AI2
4=Sensor AI3
5=Operating temp.
6=Humidity sensor
7=Operating set
8=Out AO1
9=Out AO2
10=Out AO3
Yes
VISU_TYPE_SECOND_DISP
MULTISTATE_VALUE:2174
Value displayed on display B
1=Int. sensor
2=Sensor AI1
3=Sensor AI2
4=Sensor AI3
5=Operating temp.
6=Humidity sensor
7=Operating set
8=Out AO1
9=Out AO2
10=Out AO3
11=Hour:min
12=Fan hours
13=Input 0..10V AI3
14=Switch off
Yes
FUNCTION_RIGHT_KEY
MULTISTATE_VALUE:2175
Mode key function
1=Local season c/o
2=Timer extension
3=Operating mode
Yes
MODE_FASCE
MULTISTATE_VALUE:2185
Operating mode setting
1=Without time zone
2=With time zone
3=Not occupied mode
Yes
MANUAL_OCCUPANCY
MULTISTATE_VALUE:2186
Timer extension
1=Timer extension off
2=Timer extension on
Yes
STA_MANUAL
MULTISTATE_VALUE:2187
Working season selection
Only for 2 pipe system
1=Winter
2=Summer
Yes
FAN_SPEED_MODE
MULTISTATE_VALUE:2188
Fan speed selection
1=Manual speed 1
2=Manual speed 2
3=Manual speed 3
4=Automatic speed
Yes
SEASON_BETWEEN_2P
MULTISTATE_VALUE:2214
Working season selection
in 2-pipe system with water
sensor temperature between
I15
and
I16
1=Winter
2=Summer
3=Not_defined
Yes
UNIT_VOLT_INPUT
MULTISTATE_VALUE:2217
Unit of measure on
display B for input 0...10V
1=ppm
2=rh
3=No unit
Yes
DAYLIGHT_SAVINGS_MODE
MULTISTATE_VALUE:2177
Summertime changeover
1=No
2=Yes, Europe
3=Yes, USA
Yes
H=heating;
C=cooling;
R=electric heater;
c/o=season changeover;
auto=with water sensor;
rem.=with remote contact;
par.=with parameter.
Device
The device object contains no writable property.