118/126
Object name
Object-ID
Description
Unit
Writable
EC_MIN_START_VOLT
ANALOG_VALUE:2160 Minimum EC motor starting voltage
V
Yes
EC_MAX_VOLT
ANALOG_VALUE:2161
Maximum voltage applicable to EC motor
V
Yes
EC_SW_PT_FAN
ANALOG_VALUE:2162 Starting point of EC motor in regulation
%
Yes
SPEED_EC_1
ANALOG_VALUE:2163 Speed 1 of EC motor
%
Yes
SPEED_EC_2
ANALOG_VALUE:2164 Speed 2 of EC motor
%
Yes
SPEED_EC_3
ANALOG_VALUE:2165 Speed 3 of EC motor
%
Yes
HEATER_STOP_FAN_DELAY
ANALOG_VALUE:2166 Delay on ventilation deactivation
s
Yes
FAN_START_DELAY
ANALOG_VALUE:2167 Fan start delay after valve opening
s
Yes
TIME_DELAY_ON_DESTRAT
ANALOG_VALUE:2170
Fan start time during destratification cycle
min
Yes
TIME_DELAY_OFF_DESTRAT
ANALOG_VALUE:2171 Fan stop time if regulation is not active before starting a
new destratification cycle
min
Yes
MAX_HOUR_FAN_RUN
ANALOG_VALUE:2172
Maximum fan run time before filter is considered dirty
h
Yes
TIME_TIMER_PROLUNG
ANALOG_VALUE:2178
Duration of extension timer
min
Yes
OFFSET_SETPOINT
(Note 2)
ANALOG_VALUE:2184 Offset setpoint
°C / °F
Yes
RANGE_MIN_VOLT_INPUT
ANALOG_VALUE:2215 Low limit of scale for input 0...10V
ppm
%r.h
-
Yes
RANGE_MAX_VOLT_INPUT
ANALOG_VALUE:2216 High limit of scale for input 0...10V
ppm
%r.h.
-
Yes
COR_AI3_VOLT_INPUT
(Note 4)
ANALOG_VALUE:2218 Correction for input 0...10V AI3
ppm
%r.h.
-
Yes
Note 1: the Present_Value property of WORKING_SET is calculated based on parameters setting (see
“14. Working setpoint, Economy mode and holiday
mode” page 25
. If antifreeze alarm is active or if working temperature is on alarm state, the Present_Value property is forced to the following values:
Present_Value with unit in °C (Present_Value of UNIT_C_F in CELCIUS)
Value in °C
Antifreeze alarm
70.0
Error on working temperature (heating)
-30.0
Error on working temperature (cooling)
98.0
Present_Value with unit in °F (Present_Value of UNIT_C_F in FARENHEIT)
Value in °F
Antifreeze alarm
158
Error on working temperature (heating)
-22
Error on working temperature (cooling)
209
Note 2: the Present_Value set is rounded to step 0,5 if Present_Value of UNIT_C_F is CELCIUS.
Note 3: the Present_Value set is rounded to step 0,2 if Present_Value of UNIT_C_F is FARENHEIT.
Note 4: For COR_AI3_VOLT_INPUT the Present_Value is truncated to unit if RANGE_MAX_VOLT_INPUT (Present_Value) - RANGE_MIN_VOLT_INPUT
(Present_Value) is upper than 399, otherwise the Present_Value can be set without being truncated.
Example: if range = 2000, a value set of 1.3 is truncated to 1.0.
Binary inputs
Object name
Object-ID
Description
Values
Writable
STATE_DI1
BINARY_INPUT:3000
Digital input 1 state
ACTIVE /
INACTIVE
No
STATE_DI2
BINARY_INPUT:3001
Digital input 2 state
ACTIVE /
INACTIVE
No
STATE_AI1_AS_DI3
BINARY_INPUT:3003
State of analog input 1 used as digital contact
ACTIVE /
INACTIVE
No
STATE_AI2_AS_DI4
BINARY_INPUT:3004
State of analog input 2 used as digital contact
ACTIVE /
INACTIVE
No
STATE_AI3_AS_DI5
BINARY_INPUT:3005
State of analog input 3 used as digital contact
ACTIVE /
INACTIVE
No