16/126
9. Installer parameter setting (level 2 password)
Installer parameters are password protected.
Press buttons
and
together to access the main menu. The following screen is displayed:
CLK
yMdH
(model
TH-xxCSx1
) or
AL
noAL
(model
TH-xxSSx1
)
Press
or
to display the following screen:
PAS
1
Press button and then button
until the value
11
is displayed.
Press button
to access level 1. The screen corresponding to the first level 1 parameter is displayed:
I01
0
Use button
or
to scroll through the parameters.
To modify a parameter press button and then buttons
or
to select its value.
Press button to save the value or button
ESC
to quit parameter editing mode without saving.
To quit the menu, press button
ESC
again or wait for about 120 seconds.
Parameter
Description
Default
Min
Max
I01
Internal temperature correction (K) (°C [°F])
The correction factor is added to the temperature reading of the internal sensor
I01
0
-5.0 [-9.0]
5.0 [9.0]
I02
Measured internal humidity correction (%r.H)
Correction parameter
I02
is added to the humidity reading (
TH-xxxSH1
models only)
0
-10.0
10.0
I03
External temperature correction
AI1
(K) (°C [°F])
Correction factor I03 is added to the external sensor reading
AI1
0
-5.0 [-9.0]
5.0 [9.0]
I04
External temperature correction
AI2
(K) (°C [°F])
Correction factor
I04
is added to the external sensor reading
AI2
0
-5.0 [-9.0]
5.0 [9.0]
I05
External temperature correction
AI3
(K) (°C [°F])
Correction factor
I05
is added to the external sensor reading
AI3
0
-5.0 [-9.0]
5.0 [9.0]
I06
Weighting (%) of external sensor
AI1
in relation to the internal sensor (if
M07
=0) to
create the regulation sensor.
I06
=0
→
only internal sensor used as regulation sensor
I06
=100
→
only sensor
AI1
used as regulation sensor
I06
=Y
→
sensor
AI1
and internal sensor used together to create the regulation sensor,
using the following formula Treg=[Ti (100 - Y) + (TA1 x Y)] / 100
The remote sensor
AI1
must be set as remote regulation sensor, otherwise the param-
eter
I06
is not considered
0
0
100
I07
Heating setpoint for regulation other than 4 pipe system (°C [°F])
20.0 [70]
I11
I10
I08
Cooling setpoint for regulation other than 4 pipe system (°C [°F])
25.0 [77]
I11
I10
I09
Setpoint for 4 pipe regulation (°C [°F])
21.0 [70]
I11
I10
I10
Maximum regulation setpoint value (°C [°F])
Sets a maximum limit for setpoints
I07,
I08
and
I09
40.0 [104]
I11
40.0 [104]
I11
Minimum regulation setpoint value (°C [°F])
Sets a minimum limit for setpoints
I07,
I08
and
I09
6.0 [43]
6.0 [43]
I10
I12
Economy offset (K) (°C [°F])
In economy mode, the cooling setpoint is increased by
I12
In economy mode, the heating setpoint is decreased by
I12
Example:
I12
= 3
BHS
=20 -
I12
= 17°C
BCS
=25 +
I12
= 28°C
3.0 [5]
1.0 [2]
6.0 [11]
I13
"Not occupied holiday" mode offset (K) (°C [°F])
In "not occupied holiday" mode, the cooling setpoint is increased by
I13
In "not occupied holiday" mode, the heating setpoint is decreased by
I13
Example:
I13
= 5
BHS
=20 -
I13
= 15°C
BCS
=25 +
I13
= 30°C
5.0 [9]
1.0 [2]
10.0 [18]