iDrive2 inverters Function Parameters
49
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
Traverse range: The traverse running is limited by upper
and low frequency.
The traverse range relative to the center frequency:
traverse range AW
=
center frequency×traverse range
P08.15.
Sudden
jumping
frequency
=
traverse
range
AW×sudden jumping frequency range P08.16. When run
at the traverse frequency, the value which is relative to
the sudden jumping frequency.
The raising time of the traverse frequency: The time from
the lowest point to the highest one.
The declining time of the traverse frequency: The time
from the highest point to the lowest one.
The setting range of P08.15: 0.0~100.0%(relative to the
set frequency)
The setting range of P08.16: 0.0~50.0%(relative to the
traverse range)
The setting range of P08.17: 0.1~3600.0s
The setting range of P08.18: 0.1~3600.0s
P08.25
Setting
counter value
The counter works by the input pulse signals of the HDI
terminals.
When the counter achieves a fixed number, the
multi-function output terminals will output the signal of
“fixed counting number arrival” and the counter go on
working; when the counter achieves a setting number,
the multi-function output terminals will output the signal
of “setting counting number arrival”, the counter will clear
all numbers and stop to recount before the next pulse.
The setting counting value P08.26 should be no more
than the setting counting value P08.25.
The function is illustrated as below:
0
○
P08.26
Reference
counting
value
0
○