iDrive2 inverters Function Parameters
52
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P08.42
Keypad data
control
setting
0x000~0x1223
LED ones: frequency enable selection
0:
∧
/
∨
keys adjustments are valid
1:Reserved
2:
∧
/
∨
keys adjustments are invalid
3: Reserved
LED tens: frequency control selection
0:Only valid when P00.06=0 or P00.07=0
1:Valid for all frequency setting manner
2:Invalid for multi-stage speed when multi-stage speed
has the priority
LED hundreds: action selection during stopping
0:Setting is valid
1:Valid during running, cleared after stopping
2:Valid during running, cleared after receiving the stop
command
LED thousands:
∧
/
∨
keys and digital potentiometer
Integral function
0:The Integral function is valid
1:The Integral function is invalid
0x0000
○
P08.44
UP/DOWN
terminals
control
setting
0x00~0x221
LED ones: frequency control selection
0:UP/DOWN terminals setting valid
1:UP/DOWN terminals setting invalid
LED tens: frequency control selection
0:Only valid when P00.06=0 or P00.07=0
1:All frequency means are valid
2:When the multi-stage are priority, it is invalid to the
multi-stage
LED hundreds: action selection when stop
0:Setting valid
1:Valid in the running, clear after stop
2:Valid in the running, clear after receiving the stop
commands
0x000
○
P08.45
UP terminal
frequency
increasing
integral ratio
0.01~50.00 Hz/s
0.50
Hz/s
○