iDrive2 inverters Function Parameters
41
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
motor)
6:Output voltage
7:Output power
8:Set torque value
9:Output torque
10:Analog AI1 input value
11:Analog AI2 input value
14:MODBUS communication set value 1
15:MODBUS communication set value 2
P06.17
Lower limit of
AO output
The above function codes define the relative relationship
between the output value and analog output. When the
output value exceeds the range of set maximum or
minimum output, it will count according to the low-limit or
upper-limit output.
When the analog output is current output, 1mA equals to
0.5V.
In different cases, the corresponding analog output of
100% of the output value is different. Please refer to
each application for detailed information.
Setting range of P06.18 0.00V~10.00V
Setting range of P06.19 P06.17~100.0%
Setting range of P06.20 0.00V~10.00V
Setting range of P06.21 0.000s~10.000s
0.0%
○
P06.18
Correspondi
ng AO output
to the lower
limit
0.00V
○
P06.19
Upper limit of
AO output
100.0%
○
P06.20
The
correspondin
g AO output
to the upper
limit
10.00V
○
P06.21
AO output
filter time
0.000s
○
P07 Group Human-Machine Interface
P07.00
User’s
password
0~65535
The password protection will be valid when setting any
non-zero number.
00000: Clear the previous user’s password, and make
the password protection invalid.
After the user’s password becomes valid, if the
password is incorrect, users cannot enter the parameter
menu. Only correct password can make the user check
or modify the parameters. Please remember all users’
0
○