iDrive2 inverters Function Parameters
39
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
limit of AI1
Input filter time: this parameter is used to adjust the
sensitivity of the analog input. Increasing the value
properly can enhance the anti-interference of the analog,
but weaken the sensitivity of the analog input.
Note: AI2 can support 0~10V or 0~20mA input, when
AI2 selects 0~20mA input, the corresponding voltage of
20mA is 5V. AI3 can support the output of -10V~+10V.
The setting range of P05.32:0.00V~P05.34
The setting range of P05.33:-100.0%~100.0%
The setting range of P05.34:P05.32~10.00V
The setting range of P05.35:-100.0%~100.0%
The setting range of P05.36:0.000s~10.000s
The setting range of P05.37:0.00V~P05.39
The setting range of P05.38:-100.0%~100.0%
The setting range of P05.39:P05.37~10.00V
The setting range of P05.40:-100.0%~100.0%
The setting range of P05.41:0.000s~10.000s
P05.36
AI1 input
filter time
0.100s
○
P05.37
Lower limit of
AI2
0.00V
○
P05.38
Correspondi
ng setting of
the lower
limit of AI2
0.0%
○
P05.39
Upper limit of
AI2
10.00V
○
P05.40
Correspondi
ng setting of
the upper
limit of AI2
100.0%
○
P05.41
AI2 input
filter time
0.100s
○
P06 Group Output terminals
P06.01
Y1 output
selection
0:Invalid
1:On operation
2:Forward rotation operation
3:Reverse rotation operation
4: Jogging operation
5:The inverter fault
6:Frequency detection FDT1
7:Frequency detection FDT2
8:Frequency arrival
9:Zero speed running
10:Upper limit frequency arrival
11:Lower limit frequency arrival
0
○
P06.03
Relay RO
output
1
○