70
INS
TALL
AT
O
RE
U
TENTE
MANU
TENT
O
RE
Id
Parameter
Parameter
Description
Range
Default
Customised
value
P0
Max DHW
output
Defines the maximum heat output percentage of the boiler during the
D.H.W. phase compared to the maximum heat output available
0 - 100 %
100 %
P1
Min CH output Defines in percentage the minimum output in central heating mode
0 - P2
0 %
P2
Max CH output
Defines the maximum heat output percentage of the Indoor Unit du-
ring the central heating mode compared to the maximum heat output
available
0 - 100 %
G20 = 84
G31 = 82
P3
UI P.C.B. relay
operation
0 = OFF
1 = Not available
2 =General alarm
3 = CH phase mode
4 = External gas valve power supply
5 = Not available
6 = U.I. circulator command
7= Not available
8 = Not available
9 = Not available
10 = Not available
0 - 10
0
P4
Pump function-
ing
Set this parameter from the control panel. see Par 3.6
0 - 1
0
P5
External probe
correction
If the reading of the external probe is not correct it is possible to correct
it in order to compensate any environmental factors.
-9 ÷ 9 K
0
P6
-
Not available for this model
-
-
P7
-
Not available for this model
-
-
P8
Three way delay
standby OFF UE Management of three-way commutation delay for UE switch of standby
0 - 10
3
Id
Parameter
Parameter
Description
Range
Default
Customised
value
t0
Central heating
set point mini-
mum temperature
Set this parameter from the control panel. see Par 3.6
t1
Central heating
set point maxi-
mum temperature
Set this parameter from the control panel. see Par 3.6
t2
-
Not available for this model
-
-
t3
Domestic hot
water priority
timing
Set this parameter from the control panel. see Par 3.6
t4
Central heating
ignitions timer Set this parameter from the control panel. see Par 3.6
t5
Central heating
ramp timer
Set this parameter from the control panel. see Par 3.6
t6
CH ignition delay
from TA and CR
request
Set this parameter from the control panel. see Par 3.6
t7
Display lighting
Establishes the display lighting mode.
0 :
the display lights up during use and lowers after 15 seconds of inac-
tivity. In the case of anomaly the display flashes.
1 :
display lighting off.
2 :
the display is always lit up.
0 - 2
0