3.6 PROGRAMMING VICTRIX HYBRID.
By modifying these parameters as described below, the system can
be adapted according to specific needs.
Access the “Assistenza” (Assistance) menu by pressing the right
“Menu” button and turning the main switch until selecting the de-
sired menu. Press the main switch to confirm the selection. Insert
the relative access code and customise the parameters according to
your requirements.
Service Menu
Menu item
Description
Range
Zone definition
Zone system sub-menu settings
-
System definition
Sub-menu to define the devices connected to the system
-
Thermoregulation
Temperature control setting sub-menu
-
Integration
System integration setting sub-menu
-
Heat pump
Heat pump operating parameters sub-menu
-
Information
System information sub-menu
-
Factory settings
Allows to reset all parameters with factory values
Yes / No
Service Menu -> Zone definition
Menu item
Description
Range
Default
Customised
value
Room Control
Interface
Establishes the temperature control device in use
P. Rem. / T.A.
P. Rem.
Enable Heating kit Enables operation of the heater kit
Yes / No
No
Enable Glycol
Indicates the presence of antifreeze fluid in the system
Yes / No
No
Service Menu -> System definition
Menu item
Description
Range
Default
Customised
value
Reduction function Enables a reduction of PdC noise.
No
Level 1
Level 2
Level 3
No
Minimum pump
speed
Minimum speed used value
10 - 100 %
50 %
Maximum pump
speed
Maximum speed used value
10 - 100 %
100 %
O.U. function delta T Temperature delta to be maintained with UE operation
5 - 10
5
I.U. function delta T Temperature delta to be maintained with UI operation
5 - 20
10
Pump mode
The pump can function in two ways.
- Intermittent: in “winter” mode, the circulator is managed by
the control panel or the room thermostat
- Continuous = in “Winter” mode the pump is always in operation
Inter. / conti-
nuous
Inter.
DHW hysteresis
Not used on this model
-
-
DHW priority timing
In winter mode the boiler, at the end of a domestic hot water request,
is ready to switch to central heating mode if there is an active request.
Timing sets a time period in which the indoor unit waits before chan-
ging the operating mode, in order to quickly and comfortably satisfy
an additional request for domestic hot water.
0 - 100 seconds
(10 sec step)
20 seconds
Heating start timing The indoor unit has an electronic timer, which prevents the burner
from igniting too often in central heating mode
0 - 600 seconds
(10 sec step)
180 seconds
Heating ramp timing In central heating mode, the indoor unit performs an ignition ramp
in order to reach the maximum output set
0 - 840 seconds
(10 sec step)
180 seconds
Heating start delay
The indoor unit is set to switch-on immediately after a request. In the
event of particular systems (e.g. area systems with motorised thermo-
static valves etc.) it may be necessary to delay ignition
0 - 600 seconds
(10 sec step)
0