Operation in central heating mode
3.23 LOGIC OF OPERATION.
-
Central heating mode.
Following a request during the room
heating mode, the electronics decide, according to the external
temperature, whether to activate the outdoor unit, or (with cold
temperatures) the indoor unit (Fig. 65):
The management electronics select which heat source to be used
according to the combination of the parameters set in the inte-
gration menu of the control panel. The indoor unit may activate
when the external conditions are favourable to the operation of
the outdoor unit; this may happen after a time proportional to
the “central heating integration standby time” parameter.
Alternatively, you can also set a fixed switching outdoor tem-
perature (manual mode in the parameter "integration mode"
setting the temperature with "manual activation temperature").
The DHW request is prioritised compared to a room heating
request.