1.7 WATER TREATMENT
Treating the feed water allows you to prevent prob-
lems and maintain the functionality and efficiency of
the generator over time.
The ideal pH value of the water in the central heating
system must be:
VALUE
MIN.
MAX.
PH
6.5
8
HARDNESS (°fr)
9
15
To minimise corrosion, it is essential to use a corrosion
inhibitor. In order for it to work efficiently, the metal
surfaces must be clean.
ATTENTION!
Any damage caused to the boiler, due to the formation
of build-up or corrosive water, will not be covered by
the warranty.
ATTENTION!
The models only equipped with central heating are
not suitable for hot water production for human
consumption.