18
Technical features and dimensions
Model/s:
ARES PRO 500
Condensing Boilers:
YES
Low temperature boiler:
NO
Boiler type B1:
NO
Co-generation appliance for central heating:
NO
Fitted with supplementary heating system:
NO
Mixed heating appliance:
NO
Element
Symbol
Value
Unit
Element
Symbol
Value
Unit
Nominal heat output
P
n
442
kW
Seasonal energy efficiency of central
heating
η
s
94
%
For central heating only and combination boilers: useful heat output
For central heating only and combination boilers: useful efficiency
At nominal heat output in high tempera-
ture mode (*)
P
4
441.9
kW
At nominal heat output in high tempera-
ture mode (*)
η
4
88.5
%
At 30% of nominal heat output in a low
temperature mode (**)
P
1
147.1
kW
At 30% of nominal heat output in a low
temperature mode (**)
η
1
98.2
%
Auxiliary electricity consumption
Other items
At full load
el
max
0.555
kW
Heat loss in standby
P
stby
0.95
kW
At partial load
el
min
0.053
kW
Annual electrical consumption
Q
HE
1358
GJ
In standby mode
P
SB
0.004
kW
Emissions of nitrogen oxides ref. PCI (PCS)
NO
X
53 (48)
mg /
kWh
For mixed central heating appliances
Stated load profile
Domestic hot water production efficiency
η
WH
%
Daily electrical power consumption
Q
elec
kWh
Daily gas consumption
Q
fuel
kWh
Contact information
IMMERGAS S.p.A. VIA CISA LIGURE, 95 - 42041 BRESCELLO (RE) ITALY
(*) High temperature mode means 60°C on return and 80°C on flow.
(**) Low temperature mode for condensation Boilers means 30°C , for low temperature boilers 37°C and for other appliances 50°C of return temper-
ature.
Model/s:
ARES PRO 600
Condensing Boilers:
YES
Low temperature boiler:
NO
Boiler type B1:
NO
Co-generation appliance for central heating:
NO
Fitted with supplementary heating system:
NO
Mixed heating appliance:
NO
Element
Symbol
Value
Unit
Element
Symbol
Value
Unit
Nominal heat output
P
n
540
kW
Seasonal energy efficiency of central
heating
η
s
92
%
For central heating only and combination boilers: useful heat output
For central heating only and combination boilers: useful efficiency
At nominal heat output in high tempera-
ture mode (*)
P
4
540.3
kW
At nominal heat output in high tempera-
ture mode (*)
η
4
88.5
%
At 30% of nominal heat output in a low
temperature mode (**)
P
1
175.7
kW
At 30% of nominal heat output in a low
temperature mode (**)
η
1
96.0
%
Auxiliary electricity consumption
Other items
At full load
el
max
0.590
kW
Heat loss in standby
P
stby
1.34
kW
At partial load
el
min
0.088
kW
Annual electrical consumption
Q
HE
1694
GJ
In standby mode
P
SB
0.007
kW
Emissions of nitrogen oxides ref. PCI (PCS)
NO
X
56 (50)
mg /
kWh
For mixed central heating appliances
Stated load profile
Domestic hot water production efficiency
η
WH
%
Daily electrical power consumption
Q
elec
kWh
Daily gas consumption
Q
fuel
kWh
Contact information
IMMERGAS S.p.A. VIA CISA LIGURE, 95 - 42041 BRESCELLO (RE) ITALY
(*) High temperature mode means 60°C on return and 80°C on flow.
(**) Low temperature mode for condensation Boilers means 30°C , for low temperature boilers 37°C and for other appliances 50°C of return temper-
ature.
STD.005480/001
Summary of Contents for ARES PRO 150
Page 2: ...STD 005480 001 ...