6
General information
1.5 REGULATIONS FOR INSTALLATION
The appliance must be installed in accordance with the instructions
contained in this manual.
Installation must be carried out by an authorised professional tech-
nician,
who is in charge of enforcing observance of all local and/or
national laws published in the Official Gazette, as well as all appli-
cable technical regulations.
It is necessary to observe the standards, regulations and requirements
for installation provided below, constituting a rough and non-exhaus-
tive list, in order to follow the evolution of the "state of the art".
We
would like to underline that updating the list of standards is the
responsibility of the technicians authorised to carry out installation.
Also observe the standards regarding the heating control unit, con-
struction regulations and requirements on combustion heating in the
country of installation.
The appliance must be installed, commissioned and subject to mainte-
nance in accordance with the current "state of the art". This also applies
to the hydraulic system, the flue exhaust system, the installation room
and the electrical system.
Failure to observe the above regulations will void the warranty
Attention!
If the new boiler is installed in an old system without
having washed the system, as specified in the aforesaid
paragraph, any residues in the circuit may accumulate
in the generator, causing it to clog.
If ARES PRO is being installed on a new system
, it is advisable to wash
it thoroughly, using products that are suitable for the entire system,
and install a Y-strainer with two cut-off valves on the return pipe to
the boiler, so that it can be cleaned as needed.
This filter will protect the boiler from sediments coming from the
heating system.
In both cases it is necessary to keep the head losses localised in the
primary circuit, for the correct sizing of the pump.
1.6 INSTALLATION
When the appliance is installed on existing systems, make sure that:
- The flue is suitable for condensation appliances, for the temperatures
of the combustion products, calculated and built in accordance with
regulations in force. That is it a straight as possible, water-tight and
insulated and does not have any obstructions or constrictions.
- The flue is equipped with an attachment to evacuate the condensation.
- The heating control unit is equipped with a pipe for the evacuation
of the condensation produced by the boiler.
- The electrical system is built in accordance with specific regulations
and qualified technical personnel.
- The flow rate, head and direction of flow of the circulation pumps is
appropriate.
- The fuel feed line and any existing tanks are set up in accordance with
regulations in force.
- The expansion vessels ensure complete absorption of the dilation of
the fluid contained in the system.
- Slurry and build-up have been cleaned out of the system.
Important!
National law requires the water to be treated in new
installations or renovation of heating systems and
replacement of heat generators.
If ARES PRO is being installed on existing Systems:
If it is possible to schedule the replacement, it is necessary to wash
the system preventively, with alkaline dispersants. Washing must be
carried out four weeks prior to replacement, with a system operating
between 35°C - 40°C. It is always recommended to install a filter,
however, it is obligatory above 350 kW.
STD.005480/001
Summary of Contents for ARES PRO 150
Page 2: ...STD 005480 001 ...