23
A
G
M
S
Sm
Scond
Sc
R
Instructions for the installer
3.5 CONNECTION
Danger!
The gas connection must be set up by an authorised
installation technician who must observe and apply
the contents of the legislation in force and the local
requirements of the gas supply company, as incorrect
installation can cause damage to people, animals and
property, for which the manufacturer will not be held
liable.
If you notice the smell of gas:
a) Do not work the electrical switches, the telephone
or any other object that can generate sparks;
b) Immediately open doors and windows to create an
air current that purifies the room;
c) Close the gas valves.
SAFETY VALVE DRAIN
Set up a runoff pipe with funnel and trap that lead to a
suitable drain next to the drain.
The drain must be visually controlled.
The manufacturer will not be held liable in the case of
failure to observe this precaution, where any work on
the safety valve may cause damage to people, animals
and property.
Important!
Do not mix the heating water with antifreeze or an-
ti-corrosion substances at incorrect concentrations!
This may damage the gaskets and cause noise to
develop during operation.
Immergas will not be held liable in case of damage
caused to people, animals or property due to failure
to observe the above.
The main supply pressure must be between 0.5 and 6
bar (If the pressure is higher, install a pressure reducer).
ARES
PRO
CONNECTIONS
G
Gas Inlet
[Inch]
M
Flow
[DN]
R
Return
[DN]
A
Air intake [Ø
mm]
S
Flue exhaust
fm [Ø mm]
Sm
Safety pipe cou-
pling [Inch]
Scond
Condensate drain
[Ø mm]
150
1’’
65
65
150
200
(*)
1’’
DN 40
230
1’’ ¼
65
65
250
250
1’’ ¼
DN 40
300
1’’ ¼
80
80
250
250
1’’ ½
DN 40
348
1’’ ½
80
80
250
300
1’’ ½
DN 40
400
1’’ ½
80
80
250
300
1’’ ½
DN 40
500
1’’ ½
80
80
250
300
1’’ ½
DN 40
600
1’’ ½
100
100
250
300
1’’ ½
DN 40
SC: BOILER EXHAUST
Scond: CONDENSATE DRAIN
STD.005480/001
Summary of Contents for ARES PRO 150