NOTE: Operation on an incorrectly selected supply voltage will damage the controller
Should the control panel be used in conjunction with portable generating equipment, care should be taken to ensure that
the electrical supply is within the tolerance band described above. The control panel may be stored at temperatures
0
0
between 0 C and 55 C. If stored at low temperatures and then brought into a warmer environment, condensation may
form on some components. In such a situation , this condensation should be allowed to evaporate prior to use of the
equipment. If stored at high temperature, care should be taken to ensure that humidity condensation does not enter
critical electrical components, for example the power supply. The Control Panel is designed to operate within
o
o
specification for ambient temperature between 0 C and 55 C, relative humidity up to 95% ( non-condensing ).
Switch Selection Option 110V AC (88 to 132V AC) 47 to 63Hz
AC Mains Powered
230V AC (176 to 264V AC) 47 to 63 Hz
Standard voltage and frequency range is:-
This product must be earthed in accordance with local safety regulations.
DC Low Voltage Powered
18 to 30V DC
The Control Panel leaves the factory configured for the supply voltage stated on the customers order.
!Warning !
On installation alarms will need to be configured to signal when monitored gas levels have breached safe limits. The
control panel will be shipped in a semi-configured state which must be checked and configured during commissioning to
match the applications cause and effect requirements. Failure to do so will result in an ineffective system.
Power Source
88 to 132V AC (110V AC Selected) or 176 to 264V AC (230V AC Selected)
Display
2 x 16 backlight LCD
Operating Temperature
0°c to 55°c
Operating Humidity
Up to 95% non-condensing
Resolution
0.00% or ppm Range Dependant
Update Rate
1 Second
Size (mm)
255 (H) x 265 (W) x 100 (D)
Protection Standard IP54
Inputs
Up to 4 or up to 8 x 4-20mA loops
8 analogue 4-20mA loops
Inputs
2 x RS485 data highways for up to 64 detectors (700+)
3 x configurable SPCO relays (7 Amp non conductive load)
1 x fault SPCO relays (7 Amp non conductive load)
1 x solid state audio/sounder 24VDC
Outputs (Standard)
1 x solid state visual/flasher 24VDC
Outputs (Optional)
Optional Equipment
Battery backup 1.2Ah or 2.4Ah
CE Declaration
BS EN61000-6-4 EMC Compatibility 'Emissions'
Weight
3.65 KG
BS EN 61000-6-2:2001 EMC Compatibility 'Immunity'
BS EN 61010-1: 2001 Safety requirements, electrical equipment
Who should read this manual.
This manual is intended for use by trained installers of gas detection systems who are technically competent and
have all necessary tools to undertake installation and maintenance on this type of equipment.
You should not undertake any of the procedures in this manual if you do not have access to the correct equipment,
have not undertaken training on this or similar equipment or are not technically qualified to install this equipment.
Calibration gases and test equipment is available from IGD.
Failure to install and maintain the equipment properly can render the detection system ineffective.
47 to 63 Hz 150 Watts DC Option Available
Additional 8 way relay cards, I/O Nodes
Gas Detectors
Check ratings for maximum I/O from PSU
Page 3 of 52