The TEST FIRE command
The CHANGE CHANNEL command
Factory configured versions of the Tocsin 700 are available with the capability to operate analogue
thermal rate of rise and optical smoke detectors. This mode can be used when commissioning such
detectors and provides a walk around test function.
menu.
This function can be used to move from one channel to another without exiting the ENGINEERS
TEST FIRE
06 FLAM 5% LEL
Checking (29:32)
CHANGE CHANNEL
In this mode of operation the following
display is indicated with a 30 minute
count down timer indicated on the
bottom line of the display.
Whilst in this mode the panel will
automatically reset any fire alarm
input after 5 seconds. This allows
a commissioning engineer to walk a
site triggering detector heads to
bump test them during test and
commissioning of a system.
After the 30 minute period the panel returns
to the ENGINEERS menu.
Press the jog wheel to exit ths mode
Select the mode and press the jog
wheel to move sequentially
between channels.
Page 41 of 52