Example fit
protection
diodes when
switching
external DC
loads.
A1
A2
Powering Third Party Devices
The Tocsin 700 controller has been extensively third party tested to ensure electrical
safety and EMC compliance in a number of installation formats.
The requirement to power gas shut off solenoid valves is common and so has been
tested. The following tables and wiring arrangement will allow a suitable solenoid to
operate correctly from the control panel.
In general third party devices should only be switched and NOT powered from the
Tocsin 700, (with the exception of beacons and sounders).
Connecting third party devices which may place unknown power demands on the Tocsin
700 can result in damage and/or unintended operation and so is NOT recommended.
24V
0V
Tocsin 700 Model Max Solenoid
150W Version with
50 Detectors 1.5A
8 Detectors 1.5A
60W PSU Version with
Load @ 24VDC
Do note exceed the ratings listed on this data sheet. Also note that some solenoid
valves can have significant in-rush current which may adversely affect operation and
overload the power supply.
Note this connection is
direct from the 700
PSU. Incorrect
connection can
damage the 700 and
power supply. Check
polarity before
powering