Tocsin 700 Interface wiring
Sounder Alarm
Max Current
150mA 24V DC
These 3 relays can be assigned,
named, zoned etc using the Tocsin
700 operating software.
Dedicated fault relay output, this output
is energised in normal operation
In all Cases:
Relay contact ratings.
7A @ 250V AC Non-Inductive
7A @ 30V DC Non-Inductive
Spike suppression must be fitted
Note that FAULT relays are normally
energised on power up.
Addressable control panel versions only.
See 'Addressable Sensors' Section
24V DC
24V DC
AUDIO
OUTPUT
VISUAL
OUTPUT
SOUNDER O/P
WARNING LAMP O/P
Enclosure
Ground
Enclosure
Ground
1.5mmSQ See Panel
for recommended cable
types. Typical max cable
run 1000M.
1.5mmSQ See Panel
for recommended cable
types. Typical max cable
run 1000M.
Blue
Red
Black
Red
Blue
TOCSIN 102/A
TOXIC GAS
DETECTORS
TOCSIN 102IR
FLAMMABLE GAS/
CO
2
DETECTORS
+24V DC
B
A
0V
Note Flasher on
with alarm level 1.
Buzzer on with
alarm level 2.
NO NC
COM
AL1
AL2
AL3
0V DC
4-20mA IN
+24V DC
GND
GND