L N E
PSU SET
T
O 230V
AC
5.3 Set Alarm Level Setup for Alarm Levels 1,2 and 3
01 RIS&L L = 19
01 RIS&L L = 50
C1 N RELAY = 1
C1 M RELAY = 4201
Select the ALARM 1 SETUP from the user
menu. And the following display will be
shown. Note you are now editing alarm
level 1 settings. By changing the channel
number you can check and set all alarm
level 1 settings for each channel
connected. Press and hold the jog wheel to
exit the screen then select ALARM 2 and
ALARM 3 SETUP’s.
As you enter this menu screen
the channel number will be
flashing.
Press the jog wheel to move
sequentially around the screen.
With the item you want to change
flashing rotate the jog wheel to
alter levels or options.
Gas
detector
channel
number
Falling Latching
Relay Action as:
Rising
Falling
Rising Latching
Set Alarm Level
Relay Number To
Activate When Alarm
Level Exceed
Note relay numbers 1
to 3 are included on
the main panel
located as shown here
Cable Number (1 or 2) For
Addressable Detectors and
Relays. Note this is not
relevant for Analogue
Detectors or On-board
Relays
Relay outputs can also be added onto the addressable highway
along with gas detectors to provide local relay outputs for
sounders/beacons and small solenoids etc.
on channel 01. The relay activated if this occurs is on the
addressable highway at address 4201 connected to port 1 (C1).
The alarm is Rising and Latching in operation and so must be
manually reset at the Tocsin 700 panel (RIS&L). If the T700 jog
wheel is pressed the alarm will Mute (De-activate) as the action
is set to M.
These outputs start their numbering from 4201. Up to 32
addressable relay output nodes can be added to either
addressable cable 1 or 2 (C1,C2).
This example shows an alarm set once 50ppm is exceeded
Set as N for Normal
Operation or Set as
M if you want the
relay to De-activate
when the jog wheel
is pressed to Mute
an active alarm,
Mute Action
Relay Action.
1
2
3