SmartModule CR2520
22
The life time factor 0 is interpreted as 1�
The first guard protocol is interpreted as "start guarding" even if guarding is
not yet active at that time (guard time =0)�
8.4 EMCY objects
The following error codes according to DSP-401 or DSP-301 are supported:
EMCY code
Error reg
Additional
code
Description
0x6100
0x11
0x00
"Internal Software"
Overflow of an Rx queue; e�g� frequency of the RxPDOs
is too high�
Only external reset via an entry in 1003 00
0x6101
0x11
0x00
"Internal Software"
Overflow of a Tx queue; e�g� device does not
communicate with the bus�
Only external reset via an entry in 1003 00
0x8100
0x11
0x00
"Monitoring" (Guarding Error)
No guard object is received for "guard time" x " life time
factor"�
Reset with the next communication�
0x8200
0x11
0x00
"Monitoring" (Sync Error)
For "communication cycle" no sync object is received�
Only in OPERATIONAL
Reset with the next sync OBJ or PREOP
CANopen does not provide for two identical EMCY objects to be sent
consecutively�