20
9.1.4 Timeout
If no button is pressed for 15 s during parameter setting, the unit returns to the
operating mode with unchanged values�
9.2 Settings for volumetric flow monitoring
9.2.1 Adjustment to the internal pipe width
►
Select [diA] and
set a numerical value in mm�
Set the internal pipe widths before defining values for switching limits
(SPx, rPx) and analogue limit values (ASP, AEP)�
9.2.2 Configure limit value monitoring with OUT1
► Select [Uni] and set the unit of measurement (→ 9.5.1).
►
Select [OU1] and set the switching function�
-[Hno] = hysteresis function/normally open�
-[Hnc] = hysteresis function/normally closed�
-[Fno] = window function/normally open�
-[Fnc] = window function/normally closed�
►
Select [SP1] and set the value at which the output switches�
►
Select [rP1] and set the value at which the output resets�
9.2.3 Configure limit value monitoring with OUT2
► Select [Uni] and set the unit of measurement (→ 9.5.1).
►
Select [SEL2] and set [FLOW]�
►
Select [OU2] and set the switching function�
-[Hno] = hysteresis function/normally open�
-[Hnc] = hysteresis function/normally closed�
-[Fno] = window function/normally open�
-[Fnc] = window function/normally closed�
►
Select [SP2] and set the value at which the output switches�
►
Select [rP2] and set the value at which the output resets�
9.2.4 Configure analogue value for volumetric flow
► Select [Uni] and set the unit of measurement (→ 9.5.1).
►
Select [SEL2] and set [FLOW]�
►
Select [OU2] and set the function�
-[I] = current signal proportional to volumetric flow (4…20 mA)�
►
Select [ASP] and set the value at which the minimum value is provided�
►
Select [AEP] and set the value at which the maximum value is provided�