9.5.7 Reset calibration data
►
Select [CAr]�
►
Press and hold [SET] until [----] is displayed�
►
Briefly press [Mode/Enter]�
> The values are reset to the factory setting (CGA = 100)�
9.5.8 Set standard pressure which serves as a reference for measured and
display values for volumetric flow
►
Select [rEF�P] and set the requested standard pressure
Setting range: 950���1050 hPa in steps of 1 hPa
9.5.9 Set standard temperature which serves as a reference for measured
and display values for volumetric flow
►
Select [rEF�T] and set the requested standard temperature
Setting range: 0���25 °C in steps of 1 °C
9.6 Service functions
9.6.1 Read min/max values for volumetric flow
►
Select [HI] or [LO], briefly press [Set]�
[HI] = maximum value, [LO] = minimum value�
Delete memory:
►
Select [HI] or [LO]�
►
Press and hold [Set] until [----] is displayed�
►
Briefly press [Mode/Enter]�
It makes sense to delete the memories as soon as the unit operates under
normal operating conditions for the first time�
9.6.2 Reset all parameters to factory setting
►
Select [rES]�
►
Press and hold [Set] until [----] is displayed�
►
Briefly press [Mode/Enter]�
Recommendation:
► Before the reset note down your factory settings. → 12 Factory