Field modules DP
19
6.2.2 Diagnostic message of the stand-alone modules
DP diagnosis to DP standard
Bytes
Bit
Description
0
0
No slave response (set internally by the DP master)
1
Slave in start-up mode (evaluation of parameters and configuration)
2
Configuration error
3
Ext_Diag_Data present (from byte 6)
4
Function is not supported
5
Faulty slave response (set internally by the DP master)
6
Parameterisation error
7
Slave is exchanging data with another master (set internally by the
DP master)
1
0
Slave must be re-parameterised
1
Slave with static diagnosis
2
1 (acc� to PNO specification)
3
DP watchdog is active
4
Slave is in freeze mode
5
Slave is in Sync mode
6
Reserved
7
Slave is de-activated (set internally by the DP master)
2
0-6
Reserved
7
Too many Ext_Diag_Data
3
Station address of the master with which data are transferred
4, 5
Ident� number