UK
Field modules DP
7
Firmware and hardware status
Indication on module
Declaration
Example
D� kkjjxyzu
D�22011501
kk
Calendar week
Week 22
jj
Year
of the year 2001
x
Firmware bus board
Firmware bus, version 1
y
Hardware bus board
Hardware, version 5
z
Firmware I/O board
Firmware I/O, 0 (no firmware needed for
this board)
u
Hardware I/O board
Hardware I/O, version 1
4 Connections
4.1 Fieldbus connection
The fieldbus connection is established using reverse-keyed M12x1 connectors�
4
2
1
3
5
1: not connected
2: line A
3: GND
4: line B
5: shield (also on
coupling nut)
3
1
2
4
5
1: 5 V DC
2: line A
3: GND
4: line B
5: shield (also on
coupling nut)
M12 connector for the in-coming bus line
M12 connector for the outgoing bus line
4.2 Fieldbus termination
The bus is terminated using an external terminating resistor� The modules are not
capable of fieldbus termination�
The bus termination must be accomplished externally using a connector with integrated terminating
resistor (E12315) as passive terminating resistor�
4.3 Nominal current consumption of modules connected to PROFIBUS-
DP
It is important to consider the current consumption of the individual modules for
power-feed, module protection and assessment of the voltage drop on the power
cable�
Chapter 7 contains a table with the nominal current consumption of the modules�
Summary of Contents for Ecomot300 AC2630
Page 35: ...UK Field modules DP 35 ...