Field modules DP
28
Process data
The analogue input module processes signals from 0/4���20 mA with a resolution of
16 bits�
Adjustment of the measuring values at 0���20 mA
Process data
Measured value
hex
decimal
0000
0
0 mA
3FFF
16383
10 mA
7FFF
32767
20 mA
Adjustment of the measuring values at 4���20 mA
Process data
Measured value
hex
decimal
0000
0
4 mA
3FFF
16383
12 mA
7FFF
32767
20 mA
Data representation is according to the integer number format (INT)� The process
data are entered in the default settings in the two's complement format (-1
corresponds to 0xFFFF)�