Field modules DP
20
Vendor-specific diagnosis
Bytes
Bit
Description
6
Length of Ext_Diag_Data including length byte
7
0x81 (code DPV1 diagnostic format)
8 to 15
0x00
Channel-specific diagnosis
Bytes
Bit
Description
16
0-5
0x00
6/ 7
Faulty channel number:
0x00 = error in channel 0
0x40 = error in channel 1
0x80 = error in channel 2
0xC0 = error in channel 3
17
0-5
Status byte of channel
6
General error bit (set in the event of an error)
18
0-5
6-7
Bit assignment analogue to byte 16 for another
faulty channel
19
0-5
6-7
Bit assignment analogue to byte 17 for another
faulty channel
���
60
0-5
6-7
Bit assignment analogue to byte 16 for another
faulty channel
61
0-5
6
Bit assignment analogue to byte 17 for another
faulty channel