26
ifm
Device Manual AS-i IO-Link-Gateway (AC5225) Firmware V1.16
2017-11-20
IO-Link services
Device group services
>
5.3.4
IO-Link port configuration
5213
Using the services described below the port configuration can be written or read by two IO-Link ports
each. The port configuration comprises the operating parameters of the IO-Link port and the projected
manufacturer, device and function IDs of the IO-Link device to be connected.
Request write IO-Link port configuration
Byte no.
Description write request
0
command code 21 = write device group
1
index 5 = configuration ports 1 and 2
2
length = 18
3
projected port parameters port 1 = 0x00…0xFF (→
IO-Link port parameters
(
→ page
4, 5
projected IO-Link manufacturer ID port 1
6…8
projected IO-Link device ID port 1
9, 10
projected IO-Link function ID port 1
11
projected port parameters port
2 = 0x00…0xFF (→
IO-Link port parameters
(
→ page
12, 13
projected IO-Link manufacturer ID port 2
14…16
projected IO-Link device ID port 2
17, 18
projected IO-Link function ID port 2
Reply write IO-Link port configuration
Byte no.
Description reply to write request
0
command code 85 = write device group OK
Request read IO-Link port configuration
Byte no.
Description read request
0
command code: 20 = read device group
1
index: 5 = configuration ports 1 and 2
2
length: 18
Reply read IO-Link port configuration
Byte no.
Description reply to read request
0
command code 84 = read device group OK
1
current port parameter port 1 = 0x00…0xFF (→
IO-Link port parameters
(
→ page
2, 3
projected IO-Link manufacturer ID port 1
4…6
projected IO-Link device ID port 1
7, 8
projected IO-Link function ID port 1
9
current port
parameter port 2 = 0x00…0xFF (→
IO-Link port parameters
(
→ page
10, 11
projected IO-Link manufacturer ID port 2
12…14
projected IO-Link device ID port 2
15, 16
projected IO-Link function ID port 2
Summary of Contents for AC5225