IO-Link services
Device group services
>
Event status code
6100
Event status code (without details)
Bit 7 = 0. The following code applies to bits 0...4:
Bit no.
Description
0
mode = PULSE,
type = MESSAGE,
instance = Application
eventCode = A_MESSAGE
1
mode = PULSE,
type = WARNING,
instance = Application,
eventCode = A_WARNING
2
mode = PULSE,
type = ERROR,
instance = Application
eventCode = A_PARAMETER
3
mode = PULSE,
type = ERROR,
instance = Application
eventCode = A_DEVICE
4
mode = PULSE,
type = ERROR,
instance = unknown
eventCode = S_COMM
5
reserved = 0
In this IO-Link version bit has to be set to zero.
6
invalid process data
1 = device cannot provide valid process data.
7
event details: With this type of status code bit always has to be deleted.
0 = there is no event identifier and no event code.